ULM-EZR module sensor placement guidelines:
Before adjusting sensor settings, check to make sure they have
been installed in accordance with the following guidelines:
Sensor SHOULD be located
• Between 6-10’ away from window
• Over work surfaces
Sensor should NOT be located
• Over very dark surfaces (e.g. dark carpet or furniture)
• Over highly reflective surfaces (e.g. polished floors or tables)
• Outside the daylit zone (typically beyond 15’ from window)
NOW, LIGHTOLIER makes DAYLIGHTING as EASY as 1-2-3
Install Lightolier recessed luminaires* which include a
0-10 volt dimming ballast and the #EZR option per
your Lighting Layout and connect to AC power
as you normally would any recessed
luminaire.
Install a ULM-EZR module in the ceiling, positioning it 6 to 10 feet from windows
and over a work surface (it must be within 10 ft of a luminaire).
Using the low voltage plug-in 12' long CAT5 cables provided with the
luminaires*, connect the luminaire and ULM-EZR module.
An additional CAT5 cable will be provided with each luminaire* to plug in
additional luminaires* as in a daisy chain. Up to 20 luminaires* can be
connected to a single ULM-EZR module.
ULM-EZR modules can be moved or added at any time merely by plugging or
unplugging the CAT5 cables.
Both ULM-EZR modules and fixtures have proprietary RJ45 dual receptacles for
the CAT5 cable with RJ45 plugs.
When there is no daylight, place a lightmeter on the work surface and take a
footcandle reading.
Adjust to desired footcandle level by rotating the sensor in the face of the
ULM-EZR Module.
The sensors are factory pre-calibrated to 45fc on the horizontal,
assuming standard reflectances (80/50/20), ceiling heights
(8-10’) and work surfaces (2.5’).
To return to the default setting, rotate the aperture until it ‘clicks’
back into place at the mid-point.
To get MORE light on desk from the
luminaire, close aperture by rotating
it counter-clockwise.
The lamps will get brighter.
To get LESS light on desk from
the luminaire, open aperture
by rotating it clockwise.
The lamps will dim down.
1.
1.
2.
2.
3.
3.
Ordering Guide:
The DL System is the combination of the ULM-EZR Module (UF2F-EZR) and a Lightolier recessed fluorescent fixture* with a 0-10 volt dimming ballast and
the #EZR option. This option includes integrated RJ45 receptacles and a 12 foot long CAT5 cable.
The Module and luminaire need to be ordered separately.
ULM-EZR Module: Catalog Number UL2F-EZR
DL System Fixture: Specify a Lightolier recessed fluorescent fixture* with a 0-10 volt, 2 wire, dimming ballast and then add suffix #EZR
Example: CFS2GPF232UNVM7-#EZR
M7 Denotes Advance Mark VII dimming ballast for this lamping configuration. Other lamping configurations and dimming ballast manufacturers available.
*Consult your Lightolier representative for list of DL System compatible 1' X 4', 2' X 2' and 2' X 4' recessed fluorescent fixtures.
UL2F-EZR Module