THREE PHASE CONNECTION
Electric service connection terminals
Factory installed disconnect switch
Factory wired to components
on electric panel
EARTH GROUND LUG
Connection terminal for
field supplied earth
grounding wire.
Three phase electric service
not provided by Liebert
ELECTRIC CONDUIT KNOCKOUTS
On top of electric box. Knockout size
2 in (51 mm)
ALARM AND WARNING OUTPUT RELAYS
Field supplied 24V Class 2 wire for
special alarms.
(Not to exceed 1.0A @ 24v each.)
REMOTE UNIT SHUTDOWN
Replace existing jumper between terminals
37 & 38 with normally closed switch having
a minimum 50VA rating. Use field supplied
24V Class 2 wire.
SITE MONITORING CONNECTION
Terminals 77 (-) and 78 (+) are for
connection of a 2 wire, twisted pair,
communication cable (available from
Liebert or others) for optional Sitescan.
(see user's manual).
Monitoring panel
Field supplied disconnect switch may
not be required, check local codes.
Three phase electric service
not provided by Liebert
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
Factory installed unit
disconnect switch
60HZ COMPONETS SHOWN
INTELLISLOTS
Two Liebert Intellislots for optional
OCWEB-LBDS or OC485-LBDS card.
®
®
CANBUS ISOLATOR
REV 0
PAGE 5/6
REV DATE 05/11
Liebert DCP
Liebert DCP
Page 4/5
DPN002400
REV DATE 11/11
REV 0