LG Electronics 3828A30087S Air Conditioner User Manual


 
Installation Manual 29
ENGLISH
Installation
Charging
Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line
set. Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the
refrigerant charge has to be adjusted.
Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing
are either added or removed based on 30g(0.32oz) of R-410A per meter(foot).
Example: A 30ft line set is used
5 additional ft X 0.22 ounce per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit
nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).
Confirm the refrigerant R-410A. Use manifold gauge and hose for R-410A.
12k Ø12.7mm(1/2") Ø6.35mm(1/4") 7.5(25) 7.5(25) 15(49) 20(0.22)
Pipe Size
Capacity
(Btu/h)
Suction Evap
Additional Refrigerant
g/m(oz/ft)
Standard Length
m(ft)
Max. Elevation
m(ft)
Max. length
m(ft)