6. Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 28°C(82.4°F).
During heating operation, if piping temperatures fall below 26°C(78.8°F) fan stops.
The operation diagram is as following.
7. Defrost Control
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 45 minutes passed
from starting of heating operation and more than.
Defrost ends after 10 minutes pass from starting of defrost operation or when the outdoor pipe temperature rises
over 12°C(53.6°F) even if before 10 minutes.
The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 45 minutes pass
from ending of the first defrost and more than.
INDOOR PIPE
TEMP.
INDOOR FAN
SPEED
Selecting
fan speed
OFF OFFLOW
1min
Maximum
COMPRESSOR ON
28°C(82.4°F)
26°C(78.8°F)
More than 45 minutes of
heating operation
Outdoor Pipe Temp.
Indoor Fan
Compressor
4-Way Valve
ON
ON
ON
ON
OFF
ON
OFF
HOT-
START
ON
ON OFF OFFON
12°C(53.6°F)
(Defrost OFF)
-6°C(21.2°F)
(Defrost ON)
Within
10 minutes
Defrost
Defrost
More than 45 minutes of
heating operation