LG Electronics LA120HPI Air Conditioner User Manual


 
60 Room Air Conditioner
Troubleshooting Guide
3. Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at
the bottom of the cylinder.
If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys-
tem can be charged with liquid.
(2) Purge the air from the charge hose.
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid refriger-
ant). The procedure is the same if using a gas
cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
Stopping partway will allow the gas to be dis-
charged.
If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
(5) Mount the valve stem nuts and the service
port nut.
Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
Be sure to check for gas leakage.
CAUTION
This unit is charged with R-410A.
Pay attention not to charge R-22.
\
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
Lo
Charging
cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way
valve
3-Way
valve
OPEN
Open
Check valve
(1)