LG Electronics AS-W096URH0/UBH0/UWH0/UMH0 Air Conditioner User Manual


 
44 Room Air Conditioner
If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
Temperature range by COMP SPEC varies by 10°C.
Operation
Portection from overheating of power module
Portection from overheating of compressor
T off °C
T2 °C
Heat Sink Temp.
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
T = (T off - T on)
T1 = T on + T
T2 = T on + 2
*
T
D-Pipe Temp.
COMP Freq. Free Free
Fh min
OFFFc-1 Fc-1Fc-2 Fc-2
T = (T off - T2)/2
T1 = T2 + 2
*
T
T3 = T2 + T
No. MODEL T on T off
1 AS-W096U_0 Series 85 95
2 AS-W126U_0 Series 85 95
3 AS-W096U_1 Series 85 95
4 AS-W126U_1 Series 85 95
No. MODEL T on T off
1 AS-W096U_0 Series 102 110
2 AS-W126U_0 Series 88 100
3 AS-W096U_1 Series 95 105
4 AS-W126U_1 Series 95 105