LG Electronics AS-H076PB/D/M/WL1 Air Conditioner User Manual


 
Service Manual 49
Troubleshooting Guide
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V, 60Hz)
(About AC 220/240V, 50Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01N)
Check the connection housing for contacting
Connector related to CN-POWER1, 2
Connector related to CN-MOTOR
Connector contacting of Outdoor Fan/Compressor
Display PWB Assembly Check
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector
Main PCB Board Operation Check
Items
SMPS Transformer
(Indoor unit)
- Input Voltage
- Output Voltage
IC04D(7805) Output
IC01A(Reset IC)
OSC01B(8MHz)
Replace Trans
Replace IC04D
Replace faulty parts
- About AC220V/240V
±
10% - Check the power voltage
- About DC12V
DC
+
5V
Voltage of Micom No. 36,
(DC +4.5V over) and Soldering condition.
Content Remedy
NO
YES
(After 10 seconds)