LG Electronics AMNH123DEA0 (LMN120HE) Air Conditioner User Manual


 
42 Multi type Air Conditioner
Operation
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(32.9
°F)
or more
below the setting temp, the compressor is turned off. When 0.5°C(32.9
°F)
or more above the setting temp, the
compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C(32.9
°F)
Compressor OFF Temp Setting Temp+0.5°C(32.9
°F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8
°F)
Intake Air Temp 25°C(77
°F)
24°C(75.2
°F)
Intake Air Temp<26°C(78.8
°F)
Intake Air Temp+1°C(33.8
°F)
22°C(71.6
°F)
Intake Air Temp<24°C(75.2
°F)
Intake Air Temp+0.5°C(32.9
°F)
18°C(64.4
°F)
Intake Air Temp<22°C(71.6
°F)
Intake Air Temp
Intake Air Temp<18°C(64.4
°F)
18°C(64.4
°F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37.4
°F)
or more
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned
on.
Compressor ON Temp Setting Temp
Compressor OFF Temp Setting Temp + 3°C(37.4
°F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C(68
°F)
Intake Air Temp Intake Air Temp + 0.5°C(32.9
°F)
Intake Air Temp<20°C(68
°F)
20°C(68
°F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow
speed selection key on the remote control.
On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.