Klaxon 18-980544 Smoke Alarm User Manual


 
EN54-3
Fire Alarm Device Sounder
Type B: For indoor or outdoor use
18-980544/555/556/660/662/589/622/623/664/665/666
Technical Data: Document 18-186529
0832
07
0832-CPD-0618 (Sounder-LED Beacon)
0832-CPD-0619 (Sounder-Xenon Beacon)
0832-CPD-0620 (Sounder)
Nexus 110 DC Sounder & Sounder-Beacon
Installation Instructions
Klaxon Signals Ltd, Oldham, OL4 1HW, UK
Phone +44 161 287 5555 Fax +44 161 287 5511
E-mail sales@klaxonsignals.com
Issue 6 (January 2008) 18-186458
Copyright © Klaxon Signals Ltd
www.klaxonsignals.com
T
one Tone Type Tone Description / Application Dip Switch 3rd Stage Peak Sound Sounder
(
S1/S2) Tone Level (dBA@1m) Current(mA Avg)
1. 970Hz (BS5839-1:2002) O-O-O-O-O-O 18 110 45
2
. 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O-O-O-I 1 110 44
3
. 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O-O-O-I-O 1 110 43
4
. 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O-O-O-O-I-I 1 110 25
5
. 970Hz,0.5s/630Hz, 0.5s(ApolloFireSystems EvacuateTone,BS5839-1:2002) O-O-O-I-O-O 1 110 39
6
. 554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 ) O-O-O-I-O-I 1 107 24
7. 500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) O-O-O-I-I-O 1 110 28
8. 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) O-O-O-I-I-I 1 105 9
9. 500 –1200Hz, 0.5s/0.5sOFF x3/1.5sOFF(AustraliaAS1670 Evacuation tone) O-O-I-O-O-O 1 110 13
10. 550Hz/440Hz @ 0.5Hz O-O-I-O-O-I 19 107 26
1
1. 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone) O-O-I-O-I-O 1 110 19
1
2. 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone) O-O-I-O-I-I 1 112 16
1
3. 1200Hz – 500Hz @ 1Hz (DIN 33 404) O-O-I-I-O-O 1 110 34
1
4. 400Hz O-O-I-I-O-I 18 105 21
1
5. 550Hz, 0.7s/1000Hz, 0.33s O-O-I-I-I-O 1 111 33
16. 1500Hz – 2700Hz @ 3Hz (Vandal Alarm) O-O-I-I-I-I 1 116 46
17. Simulated Bell O-I-O-O-O-O 1 112 26
18. 840Hz O-I-O-O-O-I 1 113 34
19. 660Hz O-I-O-O-I-O 10 109 31
2
0. 660Hz 1.8s ON/1.8s OFF O-I-O-O-I-I 19 108 16
2
1. 660Hz 0.15s ON/0.15s OFF O-I-O-I-O-O 19 107 17
2
2. 510Hz, 0.25s/ 610Hz, 0.25s O-I-O-I-O-I 1 107 28
2
3. 800/1000Hz 0.5s each (1Hz) O-I-O-I-I-O 1 111 44
24. 250Hz – 1200Hz @ 12Hz O-I-O-I-I-I 1 105 24
25. 500Hz – 1200Hz @ 0.33Hz. O-I-I-O-O-O 1 110 31
2
6. 2400Hz – 2900Hz @ 9Hz O-I-I-O-O-I 1 116 45
27. 2400Hz – 2900Hz @ 3Hz O-I-I-O-I-O 1 116 45
28. 800Hz – 970Hz @ 100Hz O-I-I-O-I-I 1 110 42
2
9. 800Hz – 970Hz @ 9Hz O-I-I-I-O-O 1 110 43
30. 800Hz – 970Hz @ 3Hz O-I-I-I-O-I 1 110 43
31. 800Hz, 0.25s ON/1s OFF O-I-I-I-I-O 1 108 10
32. 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) O -I - I- I -I - I 1 110 29
33. 340Hz I-O-O-O-O-O 1 106 18
34. 1000Hz I-O-O-O-O-I 18 111 47
35. 1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265) I-O-O-O-I-O 1 110 44
36. 660Hz 6.5s ON/13s OFF I-O-O-O-I-I 19 108 31
37. 1000Hz/2000Hz, 1s each I-O-O-I-O-O 1 113 41
38. 720Hz, 0.7s ON/0.3s OFF I-O-O-I-O-I 1 106 26
39. 970Hz, 0.25s ON/OFF I-O-O-I-I-O 1 110 25
40. 2800Hz, 1s ON/OFF I-O-O-I-I-I 1 113 22
41. 2800Hz 0.25s ON/OFF I-O-I-O-O-O 1 113 21
42. 2400/2900 @ 2Hz I-O-I-O-O-I 1 115 43
43. Chime, 554Hz/440Hz Single shot ‘ding dong’ I-O-I-O-I-O1 104 15
44. Chime, 554Hz/440Hz Repeating ‘ding dong’ I-O-I-O-I-I 1 107 15
45. Chime, 970Hz/800Hz Single shot ‘ding dong’ I-O-I-I-O-O 1 106 36
46. Chime, 970Hz/800Hz Repeating ‘ding dong’ I-O-I-I-O-I1 106 36
47. Hooter, Repeating I-O-I-I-I-O 1 107 13
48. Gentle alarm - Tone 2, rises slowly to full volume over 30s I -O - I- I -I - I 1 109 44
49. Time-Out Alarm – As Tone 2, cuts off after 10 mins I-I-O-O-O-O 1 109 44
50. Time-Out Alarm – As Tone 2, cuts off after 2 mins I-I-O-O-O-I 1 109 44
51. 750Hz 0.33s ON/0.51s OFF I-I-O-O-I-O 1 106 12
52. 750Hz 0.51s ON/0.33s OFF I-I-O-O-I-I 1 107 25
53. 550Hz, 0.33s/1000Hz, 0.7s I-I-O-I-O-O 1 111 41
54. 600Hz – 900Hz/ 0.9s I-I-O-I-O-I 1 109 37
55. 660Hz – 680Hz/ 0.9s I-I-O-I-I-O 1 105 33
56. 670Hz – 725Hz/ 0.9s I -I - O- I -I - I 1 107 33
57. 920Hz – 750Hz/ 0.9s I-I-I-O-O-O 1 110 41
58. 700Hz - 900Hz, 0.3s/0.6s OFF I-I-I-O-O-I 1 109 15
59. 900Hz - 760Hz, 0.6s/0.3s OFF I-I-I-O-I-O 1 110 28
60. 750Hz I -I - I- O -I - I 18 107 39
61. PowerOnly –UsewithStage3controlformanual/intermittentchimetriggering I-I-I-I-O-O 43
62. PowerOnly –UsewithStage3controlformanual/intermittentchimetriggering I- I -I - I- O -I 43
63. PowerOnly –Usewith Stage3 control for manual/intermittent horn triggering I -I - I- I -I - O 47
64. Reserved for future use I - I - I - I - I - I