4. Operation and Testing
OPERATION: The smoke alarm is operating once a fresh battery is
installed and testing is complete. When products of combustion are
sensed, the unit sounds a loud 85db pulsating alarm until the air is
cleared.
HUSH CONTROL: The “HUSH” feature has the capability of temporarily
desensitizing the alarm circuit for approximately 8 minutes. This feature
is to be used only when a known alarm condition, such as smoke from
cooking, activates the alarm. Models i9060, i9060RV and i9080 are
desensitized by pushing the “HUSH” button on the smoke alarm cover.
Models i9030, i9040, i9040RV and i9050 are desensitized by pushing
the TEST/HUSH button on the cover. If the smoke is not too dense, the
alarm will silence immediately and the Red LED will flash once every 10
seconds for approximately 8 minutes. This indicates that the alarm is in a
temporarily desensitized condition. The smoke alarm will automatically
reset after approximately 8 minutes and sound the alarm if particles of
combustion are still present. The “HUSH” feature can be used repeated-
ly until the air has been cleared of the condition causing the alarm.
NOTE: DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEA-
TURE AND SOUND A CONTINUOUS ALARM.
CAUTION: BEFORE USING THE ALARM HUSH FEATURE, IDENTIFY
THE SOURCE OF THE SMOKE AND BE CERTAIN A SAFE CONDITION
EXISTS.
FLASHING LED LIGHT:
This smoke alarm is equipped with a flashing
red indicator light. The light is located under the test button and will
flash every 40 seconds to indicate that the smoke alarm is receiving
power.
TESTING: Test by pushing the test button on the cover and holding it
down for a minimum of 5 seconds. This will sound the alarm if the elec-
tronic circuitry, horn, and battery are working. If no alarm sounds, the
unit has defective batteries or other failure. DO NOT use an open flame
to test your alarm, you could damage the alarm or ignite combustible
materials and start a structure fire.
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION.
Erratic or low sound coming from your alarm may indicate a defective
alarm, and it should be returned for service (see section 12).
NOTE: WEEKLY TESTING IS REQUIRED.
Smoke alarms are designed to minimize nuisance alarms. Cigarette
smoke will not normally set off the alarm, unless the smoke is blown
directly into the alarm. Combustion particles from cooking may set off
the alarm if the alarm is located close to the cooking area. Large quanti-
ties of combustible particles are generated from spills or when broiling.
Using the fan on a range hood which vents to the outside (non-recircu-
lating type) will also help remove these combustible products from the
kitchen. If the alarm does sound, check for fires first. If a fire is discov-
ered, get out and call the fire department. If no fire is present, check to
see if one of the reasons listed in section 2 may have caused the alarm.
5. Nuisance Alarms
6. Maintenance
BATTERY REPLACEMENT
Note: Replacement batteries are available where you purchased your
alarm.
If tamper resist pin has been used, refer to TAMPER RESIST LOCKING PIN
in section 3 for removal instructions. To replace the battery, remove the
alarm from the mounting plate by rotating the alarm in the direction of
the “OFF” arrow on the cover (see figure 8).
i9030, i9040, i9050, i9060 and i9080 Smoke Alarms are powered by a
9V carbon zinc battery (alkaline and lithium batteries may also be used).
A fresh battery should last for one year under normal operating condi-
tions. This alarm has a low battery monitor circuit which will cause the
alarm to “chirp” Approximately every 30 - 40 seconds for a minimum
of seven (7) days when the battery gets low. Replace the battery when
this condition occurs.
NOTE: ANY STATEMENTS REFERRING TO A BATTERY, APPLIES TO
BOTH BATTERIES USED WITH THE i9080
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM
BATTERY REPLACEMENT.
Carbon-zinc type: EVEREADY 1222; GOLD PEAK 1604P OR 1604S
Alkaline type: ENERGIZER 522; DURACELL MN1604, MX1604;
GOLD PEAK 1604A; PANASONIC 6AM6, 6AM-6,
6AM-6PI, 6AM6X, AND 6LR61(GA)
Lithium type: ULTRALIFE U9VL-J
Models i9040RV and i9060RV are powered by a 9V alkaline battery. A
fresh battery should last for one year under normal operating conditions.
This alarm has a low battery monitor circuit which will cause the alarm
to “chirp” approximately every 30 - 40 seconds for a minimum of seven
(7) days when the battery gets low. Replace the battery when this condi-
tion occurs.