Kidde I4618 Smoke Alarm User Manual


 
Architectural and Engineering
Specifications
The smoke alarm shall be Kidde Model i4618 or approved equal. It
shall be powered by a 120VAC, 60Hz source along with a 9V battery back-
up. The unit shall incorporate an ionization sensor with nominal sensitivity
of 0.50 to .92%/ft. The temperature operating range shall be between 40°F
and 100°F (4°C and 38°C) and the humidity operating range shall be up to
85% relative humidity.
The smoke alarm can be installed on any standard single gang electri-
cal box, up to a 4” octagon junction box. The electrical connection (to the
alarm) shall be made with a plug-in connector. A maximum of 24 Kidde
devices can be interconnected in a multiple station arrangement. The
interconnect system must not exceed the NFPA (National Fire Protection
Association) limit of 18 initiating devices, of which 12 can be smoke alarms.
With 18 initiating devices (Smoke, heat, CO, etc), interconnected, it is still
possible to interconnect 6 strobe lights and/or relay modules. The alarm
shall provide optional tamper resistance that deters removal of the unit
from the wall or ceiling. No additional pieces shall be required to activate
this feature.
The alarm shall include an easy access battery compartment that is
opened and closed by sliding the battery door. The 9V battery carrier will
ensure proper battery backup protection by not allowing the battery door
to close if the battery is placed in the unit incorrectly or if a battery is not
present.
The unit shall include a piezoelectric horn that is rated at 85 decibels
at 10 feet. The unit shall include the Smart Hush
TM
feature that silences the
unit for approximately 8 minutes if a nuisance condition occurs.
The unit shall incorporate red and green LED indicators. The green
LED (when illuminated) indicates the presence of AC power. The red LED
(located under the TEST/Hush button) has four modes of operation:
Standby Condition: The red LED will flash every 30-40 seconds to indi-
cate that the smoke alarm is operating properly. Alarm Condition: When
the alarm senses products of combustion and goes into alarm the red LED
will flash one flash per second. The flashing LED and pulsating alarm will
continue until the air is cleared. When units are interconnected, only the red
LED of the alarm that senses the smoke or is being tested (the originating
unit) will flash. All other units in the interconnected system will sound an
alarm but their red LED’s will NOT flash. Alarm Memory: This smoke alarm
is equipped with an alarm memory, which provides a visual indication when
an alarm has been activated. The red LED will illuminate for about 1.5
seconds every 16 seconds to indicate the memory condition. Smart Hush
TM
Mode: The red LED will illuminate for 1.5 seconds every 8 seconds,
indicating the smoke alarm is in the Smart Hush
TM
Mode.
The unit shall at a minimum meet the requirements of UL217, NFPA72,
and (chapter 11), The State of California Fire Marshall, NFPA101 (0ne and
two family dwellings), Federal Housing Authority (FHA), Housing and Urban
Development (HUD).
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L
N
First
Alarm
Additional
Alarms
Ordering Information
Ordering Dimensions
Number UPC I2F5 Pack Quantity (w x d x h inches) Weight Skid
21007581 0-47871-07581-2 100-47871-07581-9 Cut Case (6 units) 6.63 x 13.25 x 6.25 3 lbs 1008
21007584 0-47871-07584-3 100-47871-07584-0 Bulk Pack (36 units) 13.25 x 19.5 x 19.5 18 lbs 1296
21007585 0-47871-07585-0 100-47871-07585-7 Cut Case (4 units) 7.94 x 13.38 x 11.75 2 lbs 390
21007588 0-47871-07588-1 100-47871-07588-8 Bulk Pack (4 units) 6.5 x 9 x 6.5 2 lbs 720
21007583 0-47871-07583-6 100-47871-07583-3 Cut Case (6 units) 6.63 x 13.25 x 6.25 3 lbs 1008
Not for sale by individual unit
120V AC Wire-In Smoke Alarm
Slide Load Front Battery Door
Model i4618
Technical Specifications
Model: i4618
UPC:
0-47871-07581-2
Power Source: 120VAC (80mA Max)
Sensor: Ionization
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: Up to 85% relative humidity (RH)
Size: 5.6” in diameter x 1.8” depth
Weight: .5lbs
Interconnects: Up to 24 Kidde devices
LED: Green, receiving ac power
Red, 4 modes of operation
Warranty: 5 year limited
Installation of Smoke Alarm
The smoke alarm should be installed to comply with all local codes having jurisdiction in your area,
Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single,
continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maxi-
mum of 1000 ft. of wire can be used in the interconnect system. Use standard UL listed household
wire as required by code.
Model i4618
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-i4618 sheet rev. 12-2009
1.8”5.6”