Kidde I12060 Smoke Alarm User Manual


 
Architectural and Engineering
Specifications
The smoke alarm shall be Kidde Model i12060 or approved equal.
Itshallbepoweredbya120VAC,60Hzsourcealongwitha9Vbattery
backup. The unit shall incorporate an ionization sensor with nominal
sensitivity of 0.50 to 1.06%/ft. The temperature operating range shall
bebetween40°Fand100°F(4°Cand38°C)andthehumidityoperating
range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang
electricalbox,uptoa4”octagonjunctionbox.Theelectricalconnection
(to the alarm) shall be made with a plug-in connector. A maximum of
24Kiddedevicescanbeinterconnectedinamultiplestationarrange-
ment.TheinterconnectsystemmustnotexceedtheNFPA(NationalFire
ProtectionAssociation)limitof18initiatingdevices,ofwhich12can
besmokealarms.With18initiatingdevices(Smoke,heat,CO,etc),
interconnected, it is still possible to interconnect 6 strobe lights and/or
relay modules. The alarm shall provide optional tamper resistance that
deters removal of the unit from the wall or ceiling and locks the battery
door closed. No additional pieces shall be required to activate this feature.
The alarm shall include an easy access battery compartment that is
opened and closed by pressing on the battery door. The 9V battery carrier
will ensure proper battery backup protection by not allowing the battery
door to close if the battery is placed in the unit incorrectly or if a battery
is not present. The unit shall also provide an optional tamper resistant
switch that will prevent the battery door from being opened.
Theunitshallincludeapiezoelectrichornthatisratedat85
decibelsat10feet.TheunitshallincludetheSmartHush
TM
feature
that silences the unit for approximately 7 minutes if a nuisance
condition occurs.
TheunitshallincorporateredandgreenLEDindicators.Thegreen
LED(whenilluminated)indicatesthepresenceofACpower.TheredLED
(locatedundertheTEST/Hushbutton)hasfour modes of operation:
Standby Condition:TheredLEDwillflashevery30-40secondsto
indicate that the smoke alarm is operating properly. Alarm Condition:
When the alarm senses products of combustion and goes into alarm the
redLEDwillflashoneflashpersecond.TheflashingLEDandpulsating
alarm will continue until the air is cleared.When units are interconnected,
onlytheredLEDofthealarmthatsensesthesmokeorisbeingtested
(the originating unit) will flash. All other units in the interconnected
systemwillsoundanalarmbuttheirredLED’swillNOTflash.Alarm
Memory: This smoke alarm is equipped with an alarm memory, which
provides a visual indication when an alarm has been activated. The red
LEDwillilluminateforabout1.5secondsevery16secondstoindicate
the memory condition. Smart Hush
TM
Mode: TheredLEDwillilluminate
for1.5secondsevery8seconds,indicatingthesmokealarmisinthe
SmartHush
TM
Mode.
The unit shall at a minimum meet the requirements of UL217,
NFPA72,and(chapter11),TheStateofCaliforniaFireMarshall,NFPA101
(0neandtwofamilydwellings),FederalHousingAuthority(FHA),Housing
andUrbanDevelopment(HUD).
120V AC/DC Wire-in Smoke Alarm
Front Battery Door
Part# 21006376
Model i12060
Technical Specifications
Model: i12060
PowerSource: 120VAC (
80mA),60HZ,9Vbatterybackup
AudioAlarm: 85dBat10ft
TemperatureRange: 40˚Fto100˚F(4˚Cto38˚C)
HumidityRange: 5%-95%relativehumidity(RH)
Sensor: Ionization
Size: 5”indiameterx1.75”depth
Weight: .5lbs
Interconnects: Upto24Kiddedevices
LED: Green,receivingACpower
Red,4modesofoperation
Warranty: 10 year limited warranty
Installation of Smoke Alarm
Thesmokealarmshouldbeinstalledtocomplywithalllocalcodeshavingjurisdiction
inyourarea,Article760oftheNationalElectricCode,andNFPA72.Makecertainall
alarms are wired to a single, continuous (non-switched) power line, which is not pro-
tected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in
the interconnect system. Use standard UL listed household wire as required by code.
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L
N
First
Alarm
Additional
Alarms
Ordering Information
Ordering Dimensions Case/ Layers/ Skid
Number UPC I2F5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight
N/A 7-84908-00135-1 N/A individual* 5.75x1.5x5.75 0.5lbs N/A N/A N/A
21006376 7-84908-00135-1 107-84908-00135-8 CutCase(6units) 6.5x13.25x6 3lbs 147 7 441lbs
21005927 0-47871-05927-0 200-47871-05927-4 BulkPack(6units) 6x10.5x6 3lbs 147 7 441lbs
21006932 7-84908-00135-1 407-84908-00135-9 BulkPack(36units) 19.5x11.75x12 18lbs 24 4 432lbs.
21006933 7-84908-00135-1 307-84908-00135-2 DisplayPallet(36units) 20x24x40 20lbs. 4 1 90lbs.
21005928 0-47871-27689-9 100-47871-27689-6 CutCase(3TwinPacks) 6.5x13.25x6 3lbs 147 7 441lbs