Kidde I12040 Smoke Alarm User Manual


 
Architectural and Engineering
Specifications
The smoke alarm shall be Kidde model i12040 or approved equal. It shall be
poweredbya120VAC,60Hzsourcealongwitha9Vbatterybackup.The
unit shall incorporate an ionization sensor with nominal sensitivity of .50 to
.98%ft.Thetemperatureoperationrangeshallbebetween40˚Fand100˚F
(4˚Cand38˚C)andthehumidityoperatingrangeshallbe5%-95%relative
humidity.
The smoke alarm can be installed on any standard single gang electrical
box, up to a 4” octagon junction box. The electrical connection (to the alarm)
shall be made with a plug-in connector. A maximum of 24 Kidde devices can
be interconnected in a multiple station arrangement. The interconnect system
mustnotexceedtheNFPA(NationalFireProtectionAssociation)limitof18
initiationdevices,ofwhich12canbesmokealarms.With18initiatingdevic-
es(smoke,heat,CO,etc.),interconnected,itisstillpossibletointerconnect
6 strobe lights and or relay modules. The unit shall provide optional tamper
resistance that deters removal of the unit from the wall or ceiling.
The alarm shall include a test button that will electronically simulate the
presence of smoke and cause the unit to go into alarm. This sequence tests
theunit’selectronics,batteryandhorntoensureproperoperation.
Theunitshallincludeapiezoelectrichornthatisratedat85decibelsat
10feet.TheunitshallincludeSmartHush
TM
feature that silences the unit for
approximately 7 minutes if a nuisance condition occurs. The unit shall also
includealowbatterywarningutilizingabriefalarmchirpevery30-40sec-
onds for a minimum of seven (7) days.
TheunitshallincorporateredandgreenLEDindicators.ThegreenLED
(whenilluminated)indicatesthepresenceofACpower.TheredLED(located
undertheTEST/Hushbutton)hasfour modes of operation:
Standby Condition:TheredLEDwillflashevery30-40secondstoindicate
that the smoke alarm is operating properly. Alarm Condition: When the
alarmsensesproductsofcombustionandgoesintoalarmtheredLEDwill
flashoneflashpersecond.TheflashingLEDandpulsatingalarmwillcontinue
untiltheairiscleared.Whenunitsareinterconnected,onlytheredLEDof
the alarm that senses the smoke or is being tested (the originating unit) will
flash. All other units in the interconnected system will sound an alarm but
theirredLED’swillNOTflash. Alarm Memory: This smoke alarm is equipped
with an alarm memory, which provides a visual indication when an alarm has
beenactivated.TheredLEDwillilluminateforabout1.5secondsevery16
seconds to indicate the memory condition. Smart Hush
TM
Mode:TheredLED
willilluminatefor1.5secondsevery8seconds,indicatingthesmokealarmis
intheSmartHush
TM
Mode.
TheunitshallataminimummeettherequirementsofUL217,NFPA72,
(chapter11),TheStateofCaliforniaFireMarshall,NFPA101(Oneand
twofamilydwellings)FederalHousingAuthority(FHA),HousingandUrban
Development(HUD).Itshallalsoincludea10-yearmanufacture’slimitedwarranty.
120V AC/DC Wire-in Smoke Alarm
Battery Backup
Part Number 21006378
Model i12040
Installation of Smoke Alarm
The smoke alarm must be installed to comply with all local codes having jurisdiction
inyourarea.Allwiringshallbeinaccordancewitharticles210and300.3(B)of
theUSNationalElectricalCode,ANSI/NFPA70andNFPA72.Themultiplestation
interconnect wiring must be in the same raceway as the AC power wiring. In addi-
tion the resistance if the interconnect wiring shall be a maximum of 10 ohms.
Make certain all alarms are wired to a single, continuous (non-switched) power
line, which is not protected by a ground fault interrupter. A maximum of 1000 ft.
of wire can be used in the interconnect system. Use standard UL listed household
wire as required by code.
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L
N
First
Alarm
Additional
Alarms
Ordering Information
Technical Specifications
Model Number: i12040
UPC: 0-47871-40381-3
PowerSource: 120VAC (
80mA)with9VBatteryBackUp
Sensor: Ionization
AudioAlarm: 85dBat10ft
TemperatureRange: 40˚F(4.4˚C)to100˚F(37.8˚C)
HumidityRange: 5%-95%relativehumidity(RH)
Size: 5.6”indiameterx1.55”depth
Weight: .5lb
Interconnects: Up to 24 Kidde devices
Wiring: Quick-connectplugwith8”pigtails
LED: Red,4modesofoperation
Green, indicates AC power
Warranty: 10 year limited
*Not for sale by individual unit **Includes Wiring Adapters
Ordering Dimensions Case/ Layers/ Skid
Number UPC I2F5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight
N/A 0-47871-40381-3 N/A individual* 5.75x1.5x5.75 0.5lbs N/A N/A N/A
21006378 0-47871-40381-3 100-47871-40381-0 CutCase(6units) 6.5x13.25x6 3lbs 147 7 441lbs
21006373 0-47871-09970-2 200-47871-09970-2 BulkPack(6units) 6x10.5x6 3lbs 147 7 441lbs
21006930 0-47871-40381-3 300-47871-40381-4 DisplayPallet(36units) 20 x 24 x 40 20lbs 4 1 90 lbs
Alk.Btry21006928 0-25417-12751-5 100-25417-12751-2 CutCase(6units) 6.5x13.25x6 3lbs 147 7 441lbs
Lith.Btry21006929 0-25417-01276-7 100-25417-01276-4 CutCase(6units) 6.5x13.25x6 3lbs 147 7 441lbs
21006375** 0-47871-27552-6 100-47871-27552-3 CutCase(6units) 6.5x13.25x6 3lbs 147 7 441lbs
21006372** 0-47871-09969-9 100-47871-09969-3 CutCase(3TwinPacks) 6.5x13.25x6 3lbs 147 7 441lbs
1016 Corporate Park Drive
MebaneNC27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-i12040 sheet rev. 01-2009