Kenmore 153.330552 Water Heater User Manual


 
Installation Instructions (cont'd)
Venting (cont'd)
All vent gasesmust be completely vented to the outdoors of the
structure (dwelling). install only the draft hood provided with
the new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
Gas Piping
!
TO
CHIMNEY
VENT PIPE INSTALLATION
AWARNING
Makesure the gassuppliedisthe same type listedon the
model rating plate. The inlet gaspressuremust not exceed
10.5in.water column(2.6kPa)for natural gasor 13in.water
column (3.2kPa)for propane(L.P.)gas.The minimum inlet
gaspressurelistedonthe model rating plate isfor the pur-
poseofinputadjustment.
AWARNING ,
Ifthe gascontrolvalveissubjectedto pressuresexceeding'A
poundper squareinch(3.5kPa),the damageto the gascon-
trol valvecouldresult ina fireor explosionfrom leakinggas.
_WARNING
If the main gaslineshutoffservingall gasappliancesisused,
alsoturn "OFF" thegasat eachappliance.Leaveall gasappli.
ancesshutoffuntilthe water heaterinstallationiscomplete.
There must be a minimum of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear-
ance between single wall vent pipe and combustible material
with mortar mix, cement, or other noncombustible substance.
For other than single wall, follow vent pipe manufacturer's clear-
ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.
AWARNING
Failureto haverequired clearancesbetweenventpipingand
combustiblematerial will result in a firehazard.
AWARNING ]
Besureventpipe ispropodyconnectedto preventescapeofI
dangerousfluegaseswhichcouldcausedeadlyasphyxiation. ]
AWARNING
Chemical vapor corrosionof the flue and vent systemmay
occurif air for combustioncontainscertainchemicalvapors.
Spraycanpropellants,cleaningsolvents,refrigerator and air
conditionerrefrigerants, swimmingpool chemicals,calcium
and sodiumchloride,waxes,bleach,andprocesschemicalsare
typicalcompoundswhicharepotentiallycorrosive.
A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA 54 and the gas company con-
cerning pipe size.
There must be:
A readily accessible manual shut offvalve in the gas supply llne
serving the water heater, and
A drip leg (sediment trap) ahead of the gascontrol valve to help
prevent dirt and foreign materials from entering the gas control
valve.
A flexible gas connector or a ground joint union between the
shutoffvalve and control valveto permit servicingofthe unit.
Be sure to check all the gas piping for leaks before lil_hting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse offsoapy solution and wipe dry.
Standard Models are for installation up to 3,300 feet above sea
level.
High Altitude Models are for installation from 3,300 to 5,500
feet above sea level.
If a standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must he
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.
f AWARNING
The applianceand it_ must be leak tested
beforeplacingtheapplianceinoperation.
14