Kenmore 153.326264 Water Heater User Manual


 
11
is made with any live electrical part. The discharge opening
must not be blocked or reduced in size under any circumstances.
Excessive length, over 30 feet (9.14 m), or use of more than
four elbows can cause restriction and reduce the discharge
capacity of the valve.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. If the discharge pipe is not connected to a drain or
other suitable means, the water flow may cause property
damage.
The Discharge Pipe:
Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
Shall not be plugged or blocked.
Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both
the temperature-pressure relief valve, and the discharge pipe.
Shall terminate at an adequate drain.
Shall not have any valve between the relief valve and tank.
The temperature-pressure relief valve must be manually
operated at least once a year. Caution should be taken to ensure
that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) the
water manually discharged will not cause any bodily injury or
property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions, and
replace the temperature-pressure relief valve with a new one.
FIGURE 10.
Temperature-Pressure Relief Valve -
Optional Location
An optional temperature-pressure relief valve location is
provided on the jacket top.
If the top location is preferred, the temperature-pressure relief
valve in the side location and the counter-sunk plug in the top
location can be interchanged.
Be sure to use new pipe joint compound or put two to three
turns of teflon tape around the threaded ends of the temperature-
pressure relief valve and counter-sunk plug when reinstalling
these parts.
FIGURE 10A.