Kenmore 153.318131 Water Heater User Manual


 
Installation Instructions (cont'd)
Temperature-Pressure
Relief Valve
_,WARNING
At the time of manufacture this water heater was provided
with a combination temperature-pressures relief valve certi-
fied by a nationally recognized testing laboratory that main-
tains periodic inspection of production of listed equipment
or materials, as meeting the requirements for Relief Valves
and Automatic Gas Shutoff Devices for Hot Water Supply
Systems, and the current edition of ANSI Z21.22, CSA 4.4
and the code requirements of ASME. If replaced, the valve
must meet the requirements of local codes, but not less
than a combination temperature and pressure relief valve
certified as meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply
Systems, ANSI Z21.22 CSA 4.4 by a nationally recognized
testing laboratory that maintains periodic inspection of pro-
duction of listed equipment or materials.
The valve must be marked with a maximum set pressure
not to exceed the marked hydrostatic working pressure of
the water heater (150 Ibsdsq. in.) and a discharge capacity
not lessthan the water heater input rate as shown on the
model rating plate. (Electric heaters - watts divided by 1000
x 3412 equal BTU/Hr. rate.)
Your local jurisdictional authority, while mandating the use
of a temperature-pressure relief valve complying with ANSI
Z21.22 CSA 4.4 and ASME, may require a valve model dif-
ferent from the one furnished with the water heater.
Compliance with such local requirements must be satisfied
bythe installer or end user of the water heater with a locally
prescribed temperature-pressure relief valve installed in the
designated opening inthe water heater in place of the facto-
ry furnishedvalve.
For safe operation of the water heater, the relief valve must
not be removed from it'sdesignated opening or plugged.
The temperature-pressure relief valve must be installed
directly into the fitting of the water heater designated for
the relief valve. Position the valve downward and provide
tubing so that any discharge will exit only within 6 inches
above, or at any distance below the structural floor. Be cer-
tain that no contact is made with any live electrical part.
The discharge opening must not be blocked or reduced in
size under any circumstances. Excessivelength, over 30 feet,
or use of more than four elbows can cause restriction and
reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the
relief valve and the tank. Do not connect tubing directly to
discharge drain unless a 6" air gap is provided. To prevent
bodily injury, hazard to life, or property damage, the relief
valve must be allowed to discharge water in quantities
should circumstances demand. If the discharge pipe is not
connected to a drain or other suitable means, the water flow
may causeproperty damage.
The Discharge Pipe:
Must not be smaller insize than the outlet pipe sizeof
the valve, or haveany reducing couplings or other
restriction.
Must not be pluggedor blocked.
Must be of material listed for hot water distribution.
Must be installed so as to allow complete drainage of
both the temperature-pressure relief valve, and the dis-
charge pipe.
Must terminate at an adequate drain.
Mustnothaveanyvalvebotweenthereliefvalveandtank.
_,WARNING
The temperature-pressure relief valve must be manually
operated at least once a year. Caution should be taken to
ensure that (I) no one is in front of or around the outlet
of the temperature-pressure relief valve discharge line,
and (2) the water manually discharged will not cause any
bodily injury or property damage because the water may
be extremely hot.
If after manually operating the valve, it fails to complete-
ly reset and continues to release water, immediately,
close the cold water inlet to the water heater, follow the
draining instructions, and replace the temperature-pres-
sure relief valve with a new one.
TEMPERATURE-PRESSURE
RELIEF VALVE
DISCHARGE
PIPE
(Do not cap
or plug)
6 ,f
AIR GAP
FLOOR DRAIN
9