11
Stove Clearances Unprotected Surfaces Protected Surfaces
Top vent/vertical per NFPA 211 or CAN/CSA-B365-M
Side Rear Corner Side Rear Corner
Rear heatshield with 24" 25" 18" 10" 14" 10"
Single wall pipe 610mm 635mm 460mm 255mm 355mm 255mm
Rear heatshield with 18" 10" 14" 6" 6" 6"
Double wall pipe or shields 460mm 255mm 355mm 150mm 150mm 150mm
Stove Clearances Unprotected Surfaces Protected Surfaces
Rear Vent/Horizontal per NFPA 211 or CAN/CSA-B365-M
Side Rear Corner Side Rear Corner
Rear heatshield with 24” 25” 20” 10” 25” 18”
Single wall pipe 610mm 635mm 510mm 255mm 635mm 460mm
Rear heatshield with 18” 14” 17” 6” 6” 6”
Double wall pipe or shields 460mm 355mm 430mm 150mm 150mm 150mm
Connector Unprotected Surface Protected Surface
Clearances per NFPA 211 or CAN/CSA-B365-M
Singlewall pipe -vertical installations 18" (460mm) 6" (150mm)
Double wall pipe-vertical installations pipe mfgr. listing pipe mfgr. listing
Single wall pipe -horizontal installations 18” (460mm) 9” (230mm)
Double wall pipe-horizontal installations pipe mfgr. listing pipe mfgr. listing
Jøtul F 3 Clearances
Very important:
Top vent/vertical- assumes the connector pipe is exiting
off the top of the stove and traveling vertically. If top vented
to any horizontal runs –the stove’s position is dictated by
the connector pipe clearances.
Rear vent/horizontal- assumes the connector pipe is
existing out the rear of the stove and is traveling
horizontally to the chimney. If rear vented to vertical run –
the stove position is dictated by the connector pipe
clearances.
Dimensions in Inches represent U.S. requirements.
Dimensions in Millimeters represent Canadian
requirements.
Wall protection is discussed in further detail on page
10 of this manual.
A: Top to Mantel 34” 860 mm
B: Top to Top Trim 20” 510 mm
C: Side to Side trim 13” 330 mm
D: Side to Side Wall 24” 610 mm
USA/Canada