Johnson Controls A19A Thermostat User Manual


 
A19A
Issue 9811
Catalogue Section 1 © 2003 Johnson Controls Inc.
Order No. PD-A19A-E
8
S
pecifications
CE Conformit
y
According to low voltage directive and EMC directive
Operatin
g
ran
g
e
-35 to +290 °C. See type number selection table.
Differential
See type number selection table.
Differential ad
j
ustments
Controls with adjustable differential (types A19ABC and A19BBC) have
an adjustment lever under the cover.
Senso
r
st
y
les
Styles 1a, 1b, 2, 3, 4h, and 20 (see drawings page 3)
Electrical ratin
g
s
~15(8) A, 230 V; except A19AAF and A19DAF: ~15(3) A 230 V, and
A19ABC-9036/9037: ~15(5) A 230 V
Ambient temp. limits
-35 to +55 °C
Conduit openin
g
22.3 mm diam. hole for PG-16 connector
Material
Case 1.75 mm cold-rolled zinc plated steel
Cover 1.5 mm ABS plastic
Protection Class
IP30
Shippin
g
wei
g
ht
Individual pack 0.4 kg
Overpack 10 kg (24 pcs)
Dimensions
(see dimension drawing)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond
these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, WI, USA
European Headquarters: Westendhof 8, 45143 Essen, Germany
European Factories: Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany)
Branch Offices: Principal European Cities.