8
condensing
• Natural gas fired condensing boiler
• Meets Building Regulations 2006 (Part L2)
• Fully condensing high efficiency 85%
at 80˚C, 93% at 60˚C flow
• Compact space saving design
• Full automatic ignition
• Advanced electronic controls
Model 48 70 94 116
Boiler output (condensing)
48.83 69.84 93.65 116.25
50/30˚C
Boiler output (non-condensing)
44.63 63.84 83.60 106.30
80/60˚C
Height 1438
Width 600
Depth 723 846 969 1092
Flow/Return Connections (BSP) RC2
Gas Inlet (BSP) RC
3
/
4
RC
3
/
4
RC
3
/
4
RC1
Flue Size (mm) 150
Maximum Working Pressure (bar) 4.5
Water Content (L) 28 36 43 51
Approx Dry Weight (kg) 298 350 442 494
Front (mm) 750
Back (mm) 200
Side (mm) 50 50 50 100
General Data Concord CXC (48 - 116)
Option Kits
Boiler
Remote indication board
Outside sensor
Concord CXC
✓
✓
Concord CXC 48 - 116kW
Boiler
Clearances