CONTROL OF CH TEMPERATURE
The output temperature of CH water is adjustable from a
minimum of about 38°C to a maximum of about 85°C by
turning the knob C.
Approx CH flow temperatures for the boiler thermostat
settings:
Minimum (38 ° C)
Maximum (85 °C)
C
CONTROL OF DHW TEMPERATURE
(Mini C24, Mini C28 and Mini C32)
The temperature of the DHW leaving the boiler can be varied
from a minimum of about 35°C to a maximum of about 55°C
(within the power limits of the appliance) by turning the
temperature control knob B.
Minimum (35 ° C)
Maximum (55 ° C)
B
Adjustment of the DHW temperature is completely separate
from that of the CH circuit.
The adjustment system integrated within the boiler
automatically controls the flow of gas to the burner in order to
keep the temperature of DHW delivered constant, between
the limits of maximum and minimum output.
Where the demand is at a low level or with the temperature
set to the minimum, it is normal to see a cycle of lighting and
extinguishing of the burner when running.
Adjustment
It is advisable to adjust the DHW temperature to a level
commensurate with the demand, minimising the need to mix
with cold water. In this way, the automatic control facilities will
be fully exploited.
Moreover, where the amount of limescale present in the water
may be particularly great, not exceeding the position as
shown in the following illustration (about 50 °C) minimises
annoying incidences of scale deposits and clogging.
B
In these cases, however, it is advisable to install a small water
treatment device or softener. With such a device you should
avoid periodic descaling.
Consequently, the DHW heat exchanger will keep its
performance consistent for a longer period of time with
resulting gas savings.
TO SHUT DOWN THE BOILER
For short periods
To turn the boiler off set the function selector C to the O
position.
The appliance On lamp A will flash every 4 seconds.
For long periods
When you do not expect to use the boiler for a long period:
1 Switch the the electricity supply off.
2 Shut off the gas supply cock and the valves for the water
circuits fitted under the boiler.
3 If necessary, empty the water circuits.
FROST PROTECTION
Mini C24, Mini C28 and Mini C32 appliances are provided
with a built in anti---freeze system that operates the boiler
when the temperature is below 4 °C
Therefore, when the boiler is not lit and used in cold weather,
with consequent risk of freezing do not isolate the boiler
from the electricity supply or close the gas inlet cock.
ESCAPE OF GAS
Should a gas leak or fault be suspected contact your local
gas supplier without delay.
Do not search for gas leaks with a naked flame.
CLEANING
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains use a damp cloth and
mild detergent.
Do not use abrasive cleaning materials.
MAINTENANCE
The appliance should be serviced at least once a year by a
CORGI registered installer.
FAULTS
No heating or hot water
Check that gas and electricity are available at the boiler and
that all switches are on.
Check that the system water water pressure gauge G reads at
least 0,5 bar.
Check the lock---out signal lamp E. If it is illuminated press the
boiler reset button D to restart the ignition sequence.
Hot water but no heating
Check that the programmer and room thermostat (if fitted) are
both calling for heat.
Heating but no hot water
Check that cold water flows out of the taps at a minimum rate
of 3.5 litres per minute (or 1 pint in 10 seconds or less). If not,
look for stop valves not fully open.
If these simple checks fail to solve the problem, or the
problem recurs, consult your service engineer.
back