IDEAL INDUSTRIES 36 Boiler User Manual


 
Steel shell construction
Natural gas, oil fired or dual fuel
One or two stage operation
High efficiency 91% net (82% gross)
Reverse flame combination chamber design
Easy to install and service
Meets Building Regulations 2006 (Part L2)
Model 170 240 290 340 420 510 630 760 870 970 1100 1320 1570 1850 2200 2650 3000 3500
Output (kW) 170 240 290 340 420 510 630 760 870 970 1100 1320 1570 1850 2200 2650 3000 3500
Height 1272 1272 1372 1372 1542 1542 1542 1622 1622 1622 1622 1622 1732 1732 1892 1892 2080 2340
Width 820 820 860 860 890 890 890 1122 1122 1122 1352 1352 1462 1462 1622 1622 1670 1920
Depth 1214 1474 1411 1541 1606 1801 2113 1989 2184 2379 2346 2686 2781 3151 3225 3545 3835 3879
Flow/Return Connections (DN flange) 65 65 80 80 100 100 100 125 125 125 150 150 175 175 200 200 200 200
Flue Size (mm) 200 200 250 250 250 250 250 350 350 350 400 400 450 450 520 520 570 620
Maximum Working Pressure (bar) 6
Water Content (L) 190 251 264 298 398 462 565 671 753 836 1040 1242 1418 1617 2086 2324 2553 4862
Approx Dry Weight (kg) 435 510 588 629 796 919 1047 1341 1447 1553 1821 2030 2780 3280 4145 4465 5110 6700
Front (mm) Same length as boiler
Back (mm) 500
Side - non hinge (mm) 100
Right (mm) 200 + burner length
General Data Vanguard L (130 - 3500)
Boiler
Clearances
Vanguard L 130 - 3500kW
21