IDEAL INDUSTRIES 30 Boiler User Manual


 
5
Natural gas and propane
Single unit or modular configuration,
wall or frame mounted
Robust cast aluminium heat exchanger
Easy to install and service
Simple UK voltage system controls wiring
Modulating output down to 13kW
Wide range of flue options
Model W45 W45P W60 W60P W80 W80P
Boiler output (condensing)
13.9 - 46.9 13.7 - 45.9 13.9 - 62.3 13.6 - 60.6 21.3 - 82.7 20.7 - 80.0
50/30˚C
Boiler output (non-condensing)
12.6 - 43.7 12.6 - 58.9 19.5 - 78.2
80/60˚C
Height 900
Width 540 540 540 540 650 650
Depth 500
Flow/Return Connections (BSP) R1
1
/4
Gas Inlet (mm) 22
Flue Size (mm) 80/125 & 100/150 80/125 & 100/150 100/150
Maximum Working Pressure (bar) 4
Water Content (L)
88881010
Approx Dry Weight (kg) 87 87 88 88 101 101
Top (mm) dependant on flue
Below (mm) 300
Left (mm) 50
Right (mm) 50
General Data W (45 - 80)
Boiler
Clearances
W 45 - 80kW
Option Kits
Boiler W
Modulating sequencer kit
Programmable room thermostat kit
Control interface kit
Outside sensor kit
Tank sensor kit
Remote indication kit
Hours run meter(s)
*
BMS (0-10V) kit
Pump kit
Multi boiler frame and header kits
*Provided as standard