TEMPERATURE HIGH LIMIT SWITCH
As a safety device, a surface mounted high temperature cut-off switch with manual reset is supplied. As an
option, an immersion high temperature cut-off switch with manual reset may be provided. Either high
temperature cut-out switch is factory preset at 190°F. In the event of an over-temperature condition, the
thermostat will disengage the power from the system. The high limit must be manually reset thereafter to restart
the heater.
Manual Reset
Surface Mounted High Immersion High Temperature Cut-Off Switch
Temperature Cut-Off Switch (Optional)
(Standard)
MIXING VALVE
The mixing valve is a triple redundant, thermostatic pressure balanced
valve specifically designed for emergency safety shower/face/eyewash
application. The valve is factory mounted and piped to the water heater.
The mixing valve meets OSHA and ANSI requirements and is capable of
providing 85°F output regardless of inlet pressure and temperature
variations, and the temperature setting is tamper proof and can not be
inadvertently adjusted in the field. Alternate mixing valve tepid water set
temperatures of 70°, 75°, 80°, and 90°F are available.
AUTOMATIC AIR VENT VALVE
An automatic air vent valve is supplied in the highest point of the
system to allow trapped air in the system to escape.
DUAL TEMPERRATURE AND PRESSURE GAUGE
A combination temperature (70° - 250° F) and pressure (0 – 200 psi) gauge
with 3-inch dial is installed in the tank.
OUTER SHELL AND INSULATION
The tank is encapsulated in 3-inch thick polyurethane foam insulation. The insulation is protected by a high
impact non-corroding colorized composite protective jacket.