Honeywell WSK-24 Home Security System User Manual


 
INSTALLATION WSK-24 WIRELESS OCCUPANCY SOLUTION
3 62-0300ES—01
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained and experienced service
technician.
WARNING
Risk of electrical shock.
Can cause severe injury, property damage or
death.
Disconnect power supply before installation and
before servicing.
IMPORTANT
The thermostat may be a line voltage powered
device. All wiring must comply with national and
local electrical codes, ordinances and
regulations.
The WSK-24 must be powered by an Approved
24 Vac, Class 2, NEMA rated transformer.
Thermostat Configuration
Refer to the thermostat’s installation instructions for
programming, mounting, and wiring the thermostat.
The receiver has a normally open dry contact relay.
Therefore, the thermostat should be set so that the relay
on the thermostat is normally closed.
Use Table 2 or Table 1 to determine the desired Installer
Codes for the thermostat being used with the WSK-24.
Wiring
Prepare Thermostat for Receiver Wiring
Turn off the thermostat and remove the power source
from the thermostat.
WARNING
Risk of electrical shock.
Can cause severe injury, property damage or
death.
Disconnect power supply before servicing.
CAUTION
Equipment Damage Hazard.
Improper removal can damage the thermostat.
Carefully follow the thermostat removal directions.
Receiver and Thermostat Terminal Wiring
Table 1. MultiPRO™ Installer Setup Codes.
IS
Code
Code
Description
Option
Value Option Description
0160 Schedule Options 0 Non-Programmable
0340
(Non-
program
mable)
Remote Temp
Sensor/Remote
Setback/
Changeover
Input
5 Remote Setback
0341 Delay for Remote
Setback
0 No Delay
2 Two Minute Delay
0342 Override Option 0 No Override during
unoccupied
1 Override during
unoccupied
0343 Unoccupied
Heating Setpoint
50-65 Range is 50 to 65°F
(10 to 18°C)
0346 Unoccupied
Cooling Setpoint
75-90 Range is 75 to 90°F
(24 to 30°C)
Table 2. SuitePRO™ Installer Setup (IS) Codes.
IS
Code
Code
Description
Option
Value Option Description
19
Remote
Setback
2
Hotel Card enabled N.C. with
1 second software delay
going from UnOccupied to
Occupied;
2 minute delay going from
Occupied to UnOccupied.
4
Hotel Card enabled N.C. with
1 second software delay
going from UnOccupied to
Occupied;
30 minute delay going from
Occupied to UnOccupied.
20 Remote
Setback for
Heating
50-70 Range is 50 to 70°F
(10 to 21°C)
21 Remote
Setback for
Cooling
72-90 Range is 72 to 90°F
(22 to 32°C)
Table 3. Wiring Designations
Receiver
Harness
Wire
Typical
Thermostat
Terminals Connection
Red R 24 Vac Power
White C 24 Vac Common
White/
Brown
Sc Dry Contact; Normally
Open
Brown Sb Dry Contact; Common