Honeywell TH8000 Thermostat User Manual


 
VisionPRO
TM
TH8000 Series
9
69-2389—03
ENGLISH
Setup functions Settings & Options (factory default in bold)
0390 Dehumidication Away
Mode
0 No
1 Yes
0391 Dehumidication Away
Mode Fan Setting
0 Fan auto
1 Fan on
2 Fan circulate
0392 Dehum. Away Mode
Low Limit Temperature
Setting
76 Low limit temperature 76°F (24°C)
[Other options: 70°F to 80°F (21°C to 27°C)]
0393 Dehum. away mode
temp. setting
85 Low limit away temperature 85°F (29°C)
[Other options: 70°F to 99°F (21°C to 37°C)]
0394 Dehum. Away Mode
Dehum. Setting
65 Away humidity level 65%
[Other options: 40% to 70%]
0400 Ventilation control 0 No ventilation
1 Vent on during all periods
2 Vent off during sleep period
3 Vent on during all periods with lockouts
4 Vent off during sleep period with lockouts
0401 Number of
bedrooms
2 Two bedrooms
[Other options: 1 to 6]
0402 Size of home 10 1,000 square feet}
[Other options: 11 to 50 (1,100 to 5,000 square feet)]
0403 Ventilation level 160 CFM (cubic feet per minute)
[Other options: (30 to 195 CFM)]
0404 Max. ventilation limit 50 50% ventilation limit
[Other options: 30% to 60% or 100%]
P Meets ASHRAE 62.2 standard
F Does not meet ASHRAE 62.2 standard
0405 Ventilation fan action 1 Ventilation on forces fan on
2 Ventilation does not force fan on
0430 Ventilation lockout 0 Off
1 Lockout for high temperatures ** See page 11
2 Lockout for low temperatures ** See page 11
3 Lockout for high and low temperatures ** See page 11
0431 Ventilation high tem-
perature lockout
100 100°F (38°C): Settings 5°F apart (3°C)
[Other options: (90°F to 110°F/32°C to 43.5°C)]
0432 Ventilation low tem-
perature lockout
-10 -10°F (-23.5°C): Settings 5°F apart (3°C)
[Other options: (-20°F to 0°F/-29°C to -18°C)]
0500 Furnace lter
change reminder
0 Off 8 365-day run time
1 10-day run time 9 30 calendar days
2 30-day run time 10 60 calendar days
3 60-day run time 11 90 calendar days
4 90-day run time 12 120 calendar days
5 120-day run time 13 180 calendar days
6 180-day run time 14 365 calendar days
7 270-day run time
0502 Furnace lter
alert options
0 Timer counts Heat & Cool run time
1 Timer counts Cool run time only
0510 Humidier pad
change reminder
0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days
0520 UV lamp change
reminder
0 Off
1 1 year
2 2 years
Installer setup