10
0
NextDone
FocusPRO
™
TH6110D Programmable Thermostat
9
Installation Guide
8
1
0
1
2
3
5
9
12
13
14
15
16
System type
Changeover valve
(O/B terminal)
Fan control
(heating)
Heating cycle rate
(CPH: cycles/hour)
Compressor
cycle rate (CPH)
System setting
adjustment
Adaptive Intelli-
gent Recovery
™
Temperature
display
Compressor
protection
Schedule format
0 Gas, oil or electric heat with air conditioning
1 Heat pump
2 Heat only (2-wire systems/power to open & close zone valves/
normally open zone valves)
3 Heat only with fan
4 Cool only
0 Changeover valve (O/B terminal energized in cooling)
1 Changeover valve (O/B terminal energized in heating)
0 Gas or oil furnace — equipment controls fan in heating
1 Electric furnace — thermostat controls fan in heating
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0 Manual changeover (Heat/Cool/Off)
1 Auto changeover (Heat/Cool/Auto/Off) **See page 10
2 Auto changeover only (Auto) **See page 10
1On**See page 10
0Off
0 Fahrenheit
1 Celsius
5 Five-minute compressor off time **See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
0 5/2 (programmable weekdays and weekends)
1 5/1/1 (weekdays, Saturday & Sunday programmable)
Setup Function Settings & Options
To begin, pr
ess and hold the and
FFAANN
buttons until the display changes
Function
number
Press or to change settings
Press
NNEEXXTT
to advance to next function
Press
DDOONNEE
to exit and save settings
Setting
To begin, pr
ess and hold the and
buttons until the display changes
System test
number
Press to turn on system
Press to turn off system
Press
NNEEXXTT
to advance to next test
Press
DDOONNEE
to terminate system test
System
status
10
30
40
70
Heating system
Cooling system
Fan system
Thermostat
information
(for reference only)
0 Heat and fan turn off.
1 Heat turns on. Fan also turns on immediately if Function 1 or 3
is set to “1” (see page 8).
0 Compressor and fan turn off.
1 Compressor and fan turn on.
0 Fan turns off.
1 Fan turns on.
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System Test System Status
Installer setup Installer system test
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
NextDone
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Follow the procedure below to test the heating, cooling and fan.