Honeywell TH2000 Thermostat User Manual


 
PRO TH1000 / TH2000 Series
5
ENGLISH
Follow the procedure below to personalize and
configure the thermostat according to the heating/
cooling system.
n Press S and T for three seconds. The display
will appear as shown on the right.
o Press S or T to change the option.
p Press S and T for three seconds to advance to
the next function.
q Press Run to exit the menu and save any
changes.
NOTE
: You will also exit the menu if you press
S
and
T
for three seconds when the last function is
displayed.
1
Applicable to programmable models (TH2110D & TH2210D) only.
2
Damage can occur if the compressor is restarted too soon after shutdown. This feature
forces the compressor to wait 5 minutes before restarting. During the wait time, the
message Cool On or Heat On flashes on the screen. When the safe wait time has elapsed,
the message stops flashing and the compressor turns on.
3
Applicable to programmable models (TH2110D & TH2210D) only.
Adaptive Intelligent Recovery™ allows the thermostat to “learn” how long your furnace or
air conditioner takes to reach the set temperature. Simply program the desired times and
desired temperatures into the schedule. The thermostat will determine when to activate
heating or cooling so that the desired temperature is attained at the desired time.
Installer setup
Function
Default
setting
Options
1 Temperature display format 0
0: Fahrenheit
1: Celsius
2
Time display format
1
0
0: 12-hour display
1: 24-hour display
3 Heating cycles per hour 5
2 to 6 cycles per hour
2: 30 min (steam, gravity)
3: 20 min (hot water, 90%+ high-efficiency furnace)
4: 15 min (gas or oil)
5: 12 min (gas or oil)
6: 10 min (electric)
4 Cooling cycles per hour 3 2 to 6 cycles per hour
5
Compressor protection
2
0
0: enabled (for systems without a compressor))
1: disabled (for systems equipped with a compressor)
6
Adaptive Intelligent Recovery
3
1
0: Off
1: On
Function
number
Option
number