T87N/T87K • Owner's Manual
69-1958EFS—02 4
Fanoperationsettings:
F:Forgas or oil heating systems, leave
thefanoperationswitchinthisfactory-set
position(forsystemsthatcontrolthefanin
acallforheat).
E:Changetheswitchtothissettingforheat
pump or electric heatsystems.(Thissetting
isforsystemsthatallowthethermostat
tocontrolthefaninacallforheat,ifafan
wire is connected to the Gterminal.)
Aligntheslotsonthebasewithtabsonthe
thermostat, then push gently until the
thermostat snaps into place.
Fan operation settings (T87N)
Thermostat mounting
Thermostat
Base
Heating System Switch 1 Switch 2
Steam or gravity(1CPH) On On
High efficiency warm air Off On
(90%+),hotwater,or
heatpump(3CPH)
Gas or oil warm air Off Off
(factorysetting)(5CPH)
Electric warm air(9CPH) On Off
Move the cycle rate switches
tothepropersettingforyour
system(seetablebelow).
Cycle rate settings