5 69-0750—1
Adjust the heat anticipator lever to match the current
rating of the primary control for the proper cycle rate
(Fig. 9). Set adjustable anticipation for total current of heat
and fan control.
Locate the current rating stamped on the control or valve
(Fig. 10), or the setting given in the device instructions.
If no current rating or heat anticipator setting is given,
measure the current with an ammeter. Proceed with the
following steps.
Fig. 9—Adjust heat anticipator.
SET CLOCK
Adjust the clock by moving the minute hand in a clock-
wise direction. Do not reverse the minute hand.
When time is correctly set, the time indicator arrow
(Fig. 8) must point to the correct time and the corresponding
daytime (light) or nighttime (dark) portion of the program
dial.
Fig. 8—Set clock.
SET HEAT ANTICIPATOR
If T8090 is used on a steam system, skip to Attach
Thermostat Cover section. When used on any other heating
system, cut the two black heat anticipator jumper wires. See
Fig. 9. Follow the remaining section steps.
Fig. 10—Current rating of primary control.