Honeywell T775U Air Conditioner User Manual


 
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—07 22
Fig. 48. Setup - Outputs - Options - Min Off/On Time.
1.3.3.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or
“on time” for all relays.
1. Press the X button to display the Min Off/On value.
2. Use the S and T buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the X button to accept the seconds and
display the DI OPTIONS.
NOTES:
1. The minimum off time applies to all relay
outputs.
2. When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.
3. If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the W button
at any time.
Fig. 49. Setup - Outputs - Options - DI Options.
1.3.3.3. DI OPTIONS (digital input options)
The DI Option you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.
1. Press the X button to display the DI Option selec-
tions.
2. Use the S and T buttons to highlight DISABLE,
SETBACK, or IGNORE.
Default: DISABLE
3. Press the X button to accept the value and display
the SHOW RT option.
When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):
DISABLE disables the outputs; relays return to de-
energized state and Mod outputs return to 0% output.
SETPOINT forces the control to the setpoint
temperature.
SETBACK enables a setback temperature value to be
programmed for each output.
To program the Setback temperature with Reset,
see Fig. 73 on page 31.
To program the Setback temperature without
Reset, see Fig. 60 on page 26.
ENABLE energizes all relays to 100%. Use this option
carefully.
IGNORE causes the digital input to have no effect on
the Relay or Mod outputs.
M24610A
SETUP
OUTPUTS
OPTIONS
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
OR
MIN ON
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF
ENTER
MINIMUM
ON TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
DI OPTS
SETUP
OUTPUTS
OPTIONS
DI OPTS
SELECT DI
OPTIONS
FOR
OUTPUTS
DISABLE
SETPOINT
SETBACK
ENABLE
IGNORE
M24611A