GENERIC REMOTE BULB CONTROLLERS
T675, T678
Regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
• Suitable for applications requiring temperature control of air or liquids
where controller must be placed outside the sensing area.
• Typical uses include control of dampers and valves in heating,
cooling and heating-cooling systems.
• Fast response models (available for use in return air duct)
operate approximately four times faster than standard models.
• Controller can be mounted in any position.
Ambient temperature compensation provides good
temperature control.
CROP-TROL CONTROLLERS
T675F
Used to control an oil-burning, portable crop dryer.
• Suitable for line-voltage, low-voltage or millivolt (Powerpile) switching.
• Mounts directly on dryer with sensing bulb in
discharge air duct.
• Knob extends through case
for manual control
point adjustment.
• Differential setting wheel,
located under cover, adjusts
difference between cut-in
and cut-out temperatures.
Remote Temperature Controllers
Part Number
Setpoint
Temperature
Relay
Outputs Element Type
Capillary
Length
(Feet) Differential (˚F) Comments
T675A1045 0˚ F to 100˚ F 1 SPDT Stainless steel bulb 20 ft 3˚ F to 10˚ F Stainless Steel Bulb
T675A1102 160˚ F to 260˚ F 1 SPDT Copper bulb 20 ft 3˚ F to 10˚ F
T675A1136 0˚ F to 100˚ F 1 SPDT Copper bulb 20 ft 1˚ F fixed
T675A1425 55˚ F to 175˚ F 1 SPDT Copper bulb 20 ft 3.6˚ F to 12˚ F
T675A1458 55˚ F to 175˚ F 1 SPDT Copper bulb 5 ft 1˚ F fixed
T675A1508 0˚ F to 100˚ F 1 SPDT Copper bulb 5 ft 3˚ F to 10˚ F
Includes 107324A Duct Bulb Holder
T675A1516 0˚ F to 100˚ F 1 SPDT Copper bulb 5 ft 1˚ F fixed
Includes 107324A Duct Bulb Holder
T675A1524 55˚ F to 175˚ F 1 SPDT Copper bulb 20 ft 1˚ F fixed
T675A1532 160˚ F to 260˚ F 1 SPDT Copper bulb 5 ft 3˚ F to 10˚ F
Includes 107324A Duct Bulb Holder
T675A1540 55˚ F to 175˚ F 1 SPDT Copper bulb 5 ft 3.6˚ F to 12˚ F
Includes 107324A Duct Bulb Holder
T675A1565 0˚ F to 100˚ F 1 SPDT Copper bulb 20 ft 3˚ F to 10˚ F
Includes 107324A Duct Bulb Holder
T675A1706 0˚ F to 100˚ F 1 SPDT Fast response capillary 5 ft 3˚ F to 10˚ F
Fast response model, includes
107324A Duct Bulb Holder
T675A1722 55˚ F to 175˚ F 1 SPDT Fast response capillary 5 ft 3.6˚ F to 12˚ F
Fast response model, includes
107324A Duct Bulb Holder
T675A1771 55˚ F to 175˚ F 1 SPDT Fast response capillary 5 ft 1˚ F fixed
Fast response model, includes
107324A Duct Bulb Holder
T675A1920 -15˚ C to +35˚ C 1 SPDT Copper bulb 20 ft 1.7˚ C to 5.6˚ C
Bi-lingual French, Celsius Model
T675A2068 -15˚ C to +35˚ C 1 SPDT Copper bulb 1.5 m 1.7˚ C to 5.6˚ C Celsius model
T675A2076 -15˚ C to +35˚ C 1 SPDT Copper bulb 1.5 m 0.6˚ C fixed Celsius model
T675A2084 -15˚ C to +35˚ C 1 SPDT Copper bulb 6.1 m 1.7˚ C to 5.6˚ C Celsius model
T675A2100 15˚ C to 75˚ C 1 SPDT Copper bulb 1.5 m 2˚ C to 6.6˚ C Celsius model
T675A2118 75˚ C to 125˚ C 1 SPDT Copper bulb 1.5 m 1.7˚ C to 5.6˚ C Celsius model
T675B1002 30˚ F to 50˚ F 1 SPDT Copper bulb 10 ft Manual Reset
T675B1010 30˚ F to 50˚ F 1 SPDT Copper bulb 20 ft Manual Reset
T675B1028 -20˚ F to +50˚ F 1 SPDT Copper bulb 10 ft Manual Reset
T675F1032 80˚ F to 220˚ F 1 SPDT Copper bulb 10 ft 5˚ F to 30˚ F
T678A1015 0˚ F to 100˚ F 2 SPDT Copper bulb 20 ft
Switch: 3˚ F fixed|/Interstage: 3˚ F to 10˚ F adjustable
T678A1155 -15˚ C to +35˚ C 2 SPDT Copper bulb 5 ft 3˚ F Bi-lingual French, Celsius Model
T678A1163 5˚ F to 95˚ F 2 SPDT Copper bulb 6.1 m
Switch: 1.7˚ C fixed|/Interstage: 1.7˚ C to 5.6˚ C adjustable Celsius model
T678A1353 55˚ F to 175˚ F 2 SPDT Copper bulb 5 ft 3.6˚ F
T678A1361 55˚ F to 175˚ F 2 SPDT Copper bulb 20 ft
Switch: 3.6˚ F fixed|/Interstage: 3.6˚ F to 12˚ F adjustable
T678A1395 15˚ C to 75˚ C 2 SPDT Copper bulb 1.5 m 2˚ C Celsius model
T678A1437 0˚ F to 100˚ F 2 SPDT Copper bulb 5 ft
Switch: 3˚ F fixed|/Interstage: 3˚ F to 10˚ F adjustable
T678A1445 55˚ F to 175˚ F 2 SPDT Copper bulb 5 ft Switch: 3.6˚ F fixed|/Interstage: 3.6˚ F to 12˚ F adjustable
T678A1478 0˚ F to 100˚ F 2 SPDT Fast response capillary 5 ft Switch: 3˚ F fixed|/Interstage: 3˚ F to 10˚ F adjustable Fast response model
T678A1494 55˚ F to 175˚ F 2 SPDT Fast response capillary 5 ft
Switch: 3.6˚ F fixed|/Interstage: 3.6˚ F to 12˚ F adjustable Fast response model
T678A1627 0˚ F to 100˚ F 2 SPDT Averaging capillary 10 ft
Switch: 3.6˚ F fixed|/Interstage: 3.6˚ F to 12˚ F adjustable
T678A1692 15˚ C to 7˚5 C 2 SPDT Copper bulb 1.5 m 2˚ C Celsius model
T678C1005 55˚ F to 85˚ F 2 SPDT Copper bulb 5.5 ft 5˚ F Changeover Stat
T678F1002 55˚ F to 85˚ F 2 SPDT Copper bulb 5.5 ft 2.0˚ F