Fig. 2. Functional Profile Number 8060—LONMARK Thermostat Object (Type 09).
(Thermostat profile variables not used are grayed).
NOTE: For additional information on the L
ON
M
ARK
Functional Profile, see the L
ON
M
ARK
Application Layer Interoperability
Guidelines and the L
ON
M
ARK
Functional Profile: Thermostat. Both documents are available from L
ON
M
ARK
at internet
address: www.lonmark.org.
L
ON
W
ORKS
®
and L
ON
M
ARK
®
are registered trademarks of Echelon
®
Corporation.
nv12
nv4
nvoSpaceTemp
SNVT_ temp_p
nv5
nvoUnitStatus
SNVT_hvac_status
nv11
nv3
nv2
nvoHeatOutput
SNVT_ lev_percent
nvoEffectSetpt
SNVT_ temp_p
nvoTerminalLoad
SNVT_ lev_percent
nvoCoolOutput
SNVT_ lev_percent
Hardware
Output
Thermostat Object
Type Number 09.
Mandatory
Network
Variables
Manufacturer
Defined
Section
Optional
Network
Variables
Hardware
Input
Configuration Properties
nv13
nvoTerminalfan
SNVT_switch
nv14
nvoEnergyHoldOff
SNVT_switch
nv9
nviSetptOffset
SNVT_ temp_p
nv6
nviSpaceTemp
SNVT_ temp_p
nv8
nviApplicMode
SNVT_hvac_mode
nv7
nv10
nviOccCmd
SNVT_occupancy
nviEnergyHoldOff
SNVT_switch
nviSetpoint
SNVT_temp_p
nv1
M16087A
SNVT_time_sec
SNVT_time_sec
SNVT_temp_p
SNVT_str_asc
SNVT_temp_setpt
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
(mandatory)
(optional)
(optional)
(optional)
(mandatory)
(optional)
(optional)
(optional)
(optional)
nc49 - nciSndHrtBt
nc48 - nciRcvHrtBt
nc64 - nciMin Delta
nc17 - neiLocation
nc60 - nciSetPnts
nc79 - nciUpSPHeat
nc80 - nciLrSPHeat
nc76 - nciUpSPCool
nc77 - nciLrSPCool