Honeywell L7224 Boiler User Manual


 
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
69-1957—1 Rev. 06-06
Boiler is
cold,
house is
cold
Display is ON;
TT-LED is ON
B1 LED is ON
120 Vac at B1-
B2
If no, replace control.
If yes, check burner
and wiring
Display is ON;
TT-LED is ON
Refer to err on
display
Boiler is
hot, house
is cold
Display is ON;
TT-LED is ON
C1 LED is ON
120 Vac at C1-
C2
120 Vac at C1-C2,
check wiring to pump
Wiring ok, is pump
running? If not,
replace the pump.
If pump is running,
check for trapped air
or closed zone
valves.
Display is ON;
TT-LED is ON
C1 LED is OFF;
ZC LED is ON
b
Boiler below the
Low Limit
temperature,
wait for boiler to
go above Low
Limit
temperature.
Display is ON;
TT-LED is ON
ZC LED is
OFF
c
Boiler above
LL? If yes,
check for 120
Vac between ZC
and L2
If no 120 Vac,
replace control.
If yes, check zone
relays, circulators
and wiring.
Table 3. Troubleshooting Guide
a
.
System
Condition
Diagnostic
Condition Check Action
a
.Refer to Fig. 5 for Display and LED locations.
b
.ZC LED ON indicates ZC terminal power is OFF.
c
.ZC LED OFF indicates ZC terminal power is ON.
69-1957-1.fm Page 4 Tuesday, June 20, 2006 11:06 AM