Boiler is
cold,
house is
cold
Display is ON;
TT-LED is ON
B1 LED is ON
120 Vac at B1-
B2
• If no, replace control.
• If yes, check burner
and wiring
Display is ON;
TT-LED is ON
Refer to err on
display
—
Boiler is
hot, house
is cold
Display is ON;
TT-LED is ON
C1 LED is ON
120 Vac at C1-
C2
• 120 Vac at C1-C2,
check wiring to pump
• Wiring ok, is pump
running? If not,
replace the pump.
• If pump is running,
check for trapped air
or closed zone
valves.
Display is ON;
TT-LED is ON
C1 LED is OFF;
ZC LED is ON
b
Boiler below the
Low Limit
temperature,
wait for boiler to
go above Low
Limit
temperature.
Display is ON;
TT-LED is ON
ZC LED is
OFF
c
Boiler above
LL? If yes,
check for 120
Vac between ZC
and L2
• If no 120 Vac,
replace control.
• If yes, check zone
relays, circulators
and wiring.
Table 3. Troubleshooting Guide
a
.
System
Condition
Diagnostic
Condition Check Action
a
.Refer to Fig. 5 for Display and LED locations.
b
.ZC LED ON indicates ZC terminal power is OFF.
c
.ZC LED OFF indicates ZC terminal power is ON.
69-1957-1.fm Page 4 Tuesday, June 20, 2006 11:06 AM