Panel Capabilities
The IPGSM-4GC is compatible with specific fire panels that
use the Contact ID communications format as described in the
SIA DC-05 standard. An additional module is required (HFS-
659EN) when installing the IPGSM-4GC. See the product
installation document for details.
AlarmNet
Honeywell's AlarmNet has been the nationwide leader in
alarm communications technology since 1986. A reliable alter-
native for the transmission of alarm signals, our radio network
provides extensive coverage in the United States and Canada.
AlarmNet Network Control center processes signals from pow-
erful servers in multiple locations equipped with 24/7 infra-
structure support. The AlarmNet network consist of redundant
hardware servers, hot back-up databases and generators with
battery back-up at all locations to ensure continuity of service.
Signals from Alarm-Net are transmitted to the central station's
receivers using multiple communications paths consisting of
the Internet, radio network or toll-free POTS service.
Installation Requirements
ULC COMPLIANCE
IPGSM-4GC must be mounted in the same room and within
20 feet of the fire panel. The wiring must be routed through
conduit.
IPGSM-4GC, and all equipment used for the IP connection
(such as the router, hub, modem, etc.) shall be listed, must
be powered from an un-switched branch circuit, and be pro-
vided with appropriate standby power.
IPGSM-4GC must use the 7AH battery (not supplied) to
provide 24-hour backup capability.
NOTE: When connecting to a fire panel a line fault monitor (Model:
HFS-659EN) must be installed to monitor and report Telco troubles
per the ULC requirement.
Electrical Specifications
Transformer: 1451-UL9.
Primary: 120 VAC, 60 Hz, 850mA.
Secondary: 18VDC, 72 VA.
•Battery
One 12 V 7.0 AH lead-acid battery (not supplied).
Battery charging current minimum 1 Amp.
Battery discharge current standby 230mA, active 950mA.
IPGSM-4GC cabinet holds one 7.0 AH battery.
Cabinet Specifications
Dimensions: 14.875" H x 12.75" W x 3.0" D (37.8 cm H x 32.4
cm W x 7.6 cm D).
Color: Red.
Shipping Specifications
Weight: 5.3 lbs. (6.94 kg).
Dimensions: 15.625" H x 13.79" W x 9.25" D (39.7 cm H x
34.9 cm W x 23.9 cm D)
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 -
49°C/32 - 120°F and at a relative humidity 93% ± 2% RH (non
condensing at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15 - 27°C/60 - 80°F.
Product Line Information
IPGSM-4GC: (For Canada only): Internet and Digital Cellular
Fire Alarm Communicator Panel. Includes red cabinet with key,
wall outlet box, Dialer Capture Module, iGSM Communications
Module, antenna & mounting adapter, PowerBoost1 power
supply, LED display board, transformer, manual, & required
screws, cables, etc.
HFS-659EN: Telco line fault monitor.
GSM-ANT3DB: 3db gain external/remote antenna.
7626-50HC: 50 ft. antenna cable, low loss.
7626-25HC: 25 ft. antenna cable, low loss.
WA7626-CA: SNA to N Adapter.
7720P: IPGSM-4GC hand held programmer.
HPTCOVER:
Plug in transformer box for IPGSM communicator.
BAT-1270: Battery 12 Volts, 7 AH, sealed.
Agency Listings and Approvals
The listings and approvals below apply to the basic IPGSM-4G
communicator panel. In some cases, certain modules may not be
listed by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
ULC Listed: S789.