ADVANCED CONFIGURATION
Table 5. Advanced Configuration.
Menu Name Menu Title (LCD
top line)
Menu Options (LCD bottom
line; defaults in bold)
Menu option description Notes:
Heat Fan HEAT FAN
CONTROL
[HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or turned
on by panel in call for heat.
HVAC [PANEL] Fan control by Panel
Stage 2 Timer STAGE 2 TIMER [5 MIN] > – < [60 MIN]
[5 MIN] >
5 minutes–60 minutes Number of minutes to delay before engaging
second stage.
Purge Timer PURGE TIME [2] 3.5 5 MIN 2.0 minutes Number of minutes panel will purge following
call for heat or cool.
2 [3.5] 5 MIN 3.5 minutes
2 3.5 [5] MIN 5.0 minutes
Purge Fan FAN IN PURGE [HVAC] PANEL Fan control by HVAC Fan controlled by HVAC or panel during purge.
HVAC [PANEL] Fan control by Panel
Purge Dampers PURGE DAMPERS [UNCHANGD] OPEN Dampers Unchanged Damper position unchanged or all dampers
open during purge.
UNCHANGD [OPEN] Dampers All Open
Auto Changeover Delay CHANGEOVER
DELAY
[15] 20 30 MIN 15 minutes auto changeover timer Number of minutes to delay auto changeover
when one zone is calling for heat and another
is calling for cooling.
15 [20] 30 MIN 20 minutes auto changeover timer
15 20 [30] MIN 30 minutes auto changeover timer
DATS Enabled DISCHARGE
SENSOR
[NO] YES Disabled Enables or disables DATS. If Disabled, the
Multistage DATS Inhibit setting is Disabled.
NO [YES] Enabled
DATS High Limit DAT HIGH LIMIT [110 F] > – < [180 F]
< [160 F] >
110 deg F–180 deg F High temperature limit.
DATS Low Limit DAT LOW LIMIT [30 F] > – < [60 F]
< [40 F] >
30 deg F–60 deg F Low temperature limit.
OT Temp Enabled OT SENSOR [NO] YES Disabled Enables or disables outdoor temperature
sensor. If Disabled, the Multistage OT Temp
Lockout setting is Disabled.
NO [YES] Enabled
OT Trip Point for
Multistage Lockout
OT LOCKOUT
TEMP
[0 F] > – < [50 F]
< [50 F] >
0 deg F–50 deg F Above this temperature 2nd stage heat is
locked out.
Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES] Enabled Allow panel to downstage multistage equip-
ment when near DATS high or low limit.
[NO] YES Disabled
LCD Contrast Adjust LCD CONTRAST [1] > – < [10]
< [5] >
Contrast value 1–10 Sets LCD display contrast for ease of viewing.
Lowest contrast is 1, highest contrast is 10.
Save Changes SAVE CHANGES? [NO] YES Disabled Saves or rejects the configuration settings.
NO [YES] Enabled
Reload Defaults RELOAD
DEFAULTS?
[NO] YES Disabled Restores the panel's default configuration
settings.
NO [YES] Enabled
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 7
for instructions on using these buttons.
Press the Mode button until the Wireless LED lights
up. The TrueZONE must be configured for wireless
devices to select Wireless mode.
4
CONNECT WIRELESS DEVICES
HOME
MODE
BACK NEXT
CONFIG
CHECK OUT
ADJUST SETTING
M28194
WIRELESS
Press Next to add devices.
While the display alternates the Press Connect and
Exit screens, push the Connect button(s) on the wire-
less device(s).
-OR-
Follow the instructions that came with the wireless
device(s).
Press Next to exit.
Fig. 15