Honeywell H7635C Smoke Alarm User Manual


 
H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
63-2579—3 6
APPENDIX
RH Test and Configuration DIP Switch Settings (Table 3)
IMPORTANT
Only adjust these switches for troubleshooting or
recalibrating the sensor. (Adjustment is not
normally necessary.)
For normal operation, always keep DIP switch 3
in the ON position. When DIP switch 3 is off, the
RH transmitter cannot read the sensor. This
inability-to-read forces the output to never
change.
Table 3. Test/Calibration Settings (Six-Switch Block).
0% RH Output (for Testing Only)
Transmitter always outputs a signal of 4 mA or 0 Vdc. The
sensor does not affect the transmitter output.
50% RH Output (for Testing Only)
Transmitter always outputs a signal of 12 mA, 2.5 VDC, or
5 VDC. The sensor does not affect transmitter output.
100% RH Output
Transmitter always outputs a signal of 20 mA, 5 VDC, or
10 VDC. The sensor does not affect the transmitter
output. Sensor doesn’t affect the transmitter output.
Normal Operating Condition
DIP switch 3 must be set in the On position for normal
operation. All other DIP switches must be set Off.
Setting 654321
Normal Operation (Default) On
0% RH Output On—————
50% RH Output —On————
100% RH Output On
Increment RH Output On
Decrement RH Output —————On
Reset to Original Calibration On On