Honeywell Series 4 Boiler User Manual


 
Part number 550-141-893/0800
7
AHE Series 4 Direct Vent Wall-Mounted Boilers — User’s Information Manual
Main burner flames
1. See Figure 4. Remove burner input plenum cover
plate “A”.
2. Visually inspect burner flames:
Proper main burner flame (see Figure 5):
a. Yellow-orange streaks may appear (caused
by dust).
Improper main burner flame:
a. Overfired — Large flames.
b. Underfired — Small flames.
c. Lack of primary air — Yellow tipping on
flames (sooting will occur).
Figure 5 Main burner flame, typical
26024
Transparent
blue flame
Inner flame
User maintenance procedures continued
Test low water cutoff
Test the low water cutoff periodically during the heating
season, following the low water cutoff manufacturer’s
instructions.
Clean vent termination and air
intake screens
1. Remove all lint and debris from both the boiler air
intake screen and the flue discharge screen.
2. The boiler control module will sense blockage of
the air intake or flue and lockout if the blockage is
excessive. It will signal by flashing the appropriate
indicator lights on the control board.
3. If removing the debris does not allow the boiler to
operate correctly afterwards, contact your qualified
service technician to inspect the boiler and vent/
air systems.
Periodically .......... Monthly .....................
89301
Figure 4