Honeywell C7021D Smoke Alarm User Manual


 
SERIES 2000 ELECTRONIC TEMPERATURE SENSORS
3 63-2590—05
C7023F Outdoor air
-40° to 158°F
(-40° to 70°C)
250°F (121°C)
10K Ohms NTC @
77° F Type III
C7023J Duct discharge air
(averaging sensor
with 4 elements)
12 ft (3.7m)
-40° to 250°F
(-40° to 121°C)
C7023K Hot water (strap-on
mounting)
f
C7023N Water / Air (bullet
probe)
C7023P Space air
temperature (button
probe)
C7023R Duct discharge air
(rigid copper
averaging sensor)
12 ft (3.7m) or 24
ft (7.3m)
-40° to 250°F
(-40° to 121°C)
C7031B Duct discharge air 6 in. (152 mm) -40° to 250°F
(-40° to 121°C)
250°F (121°C)
1097 at 77° (25°C)
c
2.1 (3.9)
C7031D Hot or chilled water 5 in. (127 mm) 40° to 350°F
(4° to 115°C)
370°F (187°C)
1097 at 77° (25°C)
c
2.1 (3.9)
C7031G
-2006
Outdoor air -40° to 120°F
(-40° to 49°C)
120°F (49°C)
1715 at 90°F (32°C)
c
2.2 (3.4)
C7031G
-2014
d
Outdoor air
-40° to 120°F
(-40° to 49°C)
120°F (49°C)
3484 at 77°F (25°C)
c
2.1 (3.9)
C7031J Duct discharge air
(averaging sensor
with 4 elements)
12 ft (3.7m) 40° to 180°F
(4° to 82°C)
250°F (121°C)
1097 at 77° (25°C)
c
2.1 (3.9)
C7041B Duct discharge air 6 in. (152 mm) or
12 in. (305 mm)
-40° to 250°F
(-40° to 121°C)
250°F (121°C)
20K Ohms NTC at
77°F (25°C)
e
C7041C Duct discharge air 18 in. (457 mm)
C7041D
Hot or chilled water
b
5 in. (127 mm)
C7041F Outdoor air -40° to 158°F
(-40° to 70°C)
C7041J Duct discharge air
(averaging sensor
with 4 elements)
12 ft (3.7m)
-40° to 250°F
(-40° to 121°C)
C7041K Hot water (strap-on
mounting)
f
C7041N
Water / Air (bullet
probe)
C7041P Space air
temperature (button
probe)
C7041R Duct discharge air
(rigid copper
averaging sensor)
12 ft (3.7m) or
24 ft (7.3m)
Table 1. Sensor Selection and Application Guide
Model Control Application
Element
Insertion Length
Element
Operating Range
Element Max
Ambient
Temperature
Sensor Resistance
in Ohms Sensitivity
a