E1237
REPLACING AN R4140M OR R4150M WITH
PREIGNITION INTERLOCKS WITH A
BC7000L/PM720M2002
2. DISCONNECT DAMPER CONTROL WIRE FROM TERMINAL 10
AND CONNECT IT TO TERMINAL 11.
3.
4.
5.
REMOVE JUMPER FROM TERMINAL BETWEEN TERMINAL 11
AND 12 (on some models).
IF LOW FIRE SWITCH IS NOT USED, CONNECT JUMPER WIRE
BETWEEN TERMINALS 8 AND 13.
JUMPER TERMINALS 8 TO 15 FOR 30-SECOND PURGE.
E1237