Honeywell ADT-HRSI Smoke Alarm User Manual


 
ADT-HRSI INTELLIGENT HEAT DETECTOR
Home and Building Control Home & Building Control European Centre of Excellence
Honeywell Inc. Honeywell GmbH
Fire Solutions
Honeywell Plaza Honeywellstrasse Lovelace Road, Southern Industrial Area
P.O. Box 524 63477 Maintal 1 Bracknell, Berkshire, RG12 8WD
Minneapolis MN 55408-0524 Germany United Kingdom
EN0C-0746E 0599R0-OB Printed in U.S.A.
SPECIFICATIONS
Heat Sensor:
Combination fixed temperature and rate of rise, alarms at
57°C (135°F) ambient or temp. increases greater than
9°C (15°F) per min.
Detector Spacing:
70ft (21.3m) center to center
Environmental Limits:
Temperature: 32° to 100°F (0° to 38°C)
Humidity: 0 to 93% rh, non-condensing
Voltage:
15.2 to 19.95 Vdc (19 Vdc nominal)
Operating Current:
Stand-by: 45µA at 19V
Alarm: 45µA at 19V
Emergency stand-alone alarm mode: 18mA
Pulse current: 100µA (100 msec)
During communication: 9 mA max.
Construction:
High impact engineering polymer
Finish:
White
Compatible Mounting Bases:
SIGA-SB standard base
ADT-RB relay base
ADT-IB and ADT-IBS isolator base
LED Operation:
On-board green LED: Flashes when polled
On-board red LED: Flashes when in alarm
Both LEDs: On steady when in alarm (stand-alone)
Compatible remote red LED:
Flashes when in alarm
Compatibility:
Signature loop controller
Address Requirements:
1 device address
Accessories:
SIGA-SB: Detector mounting base
ADT-RB: Detector mounting base with relay
ADT-IB: Detector mounting base with fault isolator
ADT-IBS: Same as above, with loop continuity switch
SIGA-LED: Remote alarm LED
SIGA-TS: Trim skirt (supplied with 4in bases)
74-3346 J.S. 12-99