Honeywell 8000 Thermostat User Manual


 
2 3 4 5
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
Patents Pending. All Rights Reserved
69-1871-1 M.S. Rev. 09-06
Press and hold these two blank buttons until the
display changes.
DONE
CANCEL
SYSTEM
HEAT
M24080
Use arrows to change settings as required.
DONE
FUNCTION
SETTING
M24082
Press DONE to exit and save settings.
INSTALLER SETUP FUNCTIONS
Available option and default settings vary by thermostat.
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0120 Year (rst two
digits)
20 (2000-2099)
21 (2100-2178)
0130 Year (second two
digits)
06 (2006) [Other options 0-99]
0140 Month 6 [Other options 1-12]
0150 Day 15 [Other options 1-31]
0160 Schedule format 4 7-day programming
0 Non-programmable
2.
3.
4.
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0170 System type 1 1 heat / 1 cool Conv.
2 1 heat / 1 cool heat
pump (no Aux. heat)
3 Heat only (2 wire)
4 Heat only with fan
5 Hot water Series 20
6 Cool only
7 2 heat / 1 cool heat
pump (with Aux. heat)
8 2 heat / 2 cool multistage
9 2 heat / 1 cool multistage
10 1 heat / 2 cool multistage
11 2 heat / 2 cool heat pump
(no Aux. heat)
12 3 heat / 2 cool heat
pump (with Aux. heat)
0180 Fan control
(heating)
0 Gas/Oil heat (equipment
controls heating fan)
1 Electric furnace (thermo-
stat controls heating fan)
0190 Changeover valve
(O/B terminal)
0 Controls valve in cooling
1 Controls valve in heating
0200 Auxiliary heat 0 Electric backup heat
1 Fossil fuel backup heat
0210 External fossil
fuel kit
1 External fossil fuel kit
controls backup heat
0 Thermostat controls
backup heat (outdoor
sensor required)
0220 First stage
compressor cycle
rate
3 Recommended
[Other options: 1–6]
0230 Second stage
compressor cycle
rate
3 Recommended
[Other options: 1–6]
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0240 First stage heat
cycle rate
5 Gas or oil furnaces of
less than 90%
efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
0250 Second stage
heat cycle rate
5 Gas or oil furnaces of
less than 90% efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
0260 Third stage heat
cycle rate
9 Electric auxiliary heat
or electric furnaces
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
5 Gas or oil furnaces of
less than 90% efciency
[Other options: 1–12]
0270 Emergency heat
cycle rate
9 Electric auxiliary heat
or electric furnaces
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
5 Gas or oil furnaces of
less than 90% efciency
[Other options: 1–12]
0280 Backlight 0 Backlight on keypress
1 Continuous backlight (re-
quires 24VAC connection)
0300 Manual/auto
changeover
0 Manual changeover
(Heat/Cool/Off)
1 Automatic changeover
(Heat/Cool/Auto/Off)
Table 1. Installer Setup
Setup functions Setting & Options (factory
default in bold)
0310 Auto changeover
deadband
3 Heat/cool tempera-
ture 3°F apart (1.5°C)
[Other options: 2-9 (2°F-
9°F/1°C-5°C)]
0320 Temperature
display
0 Fahrenheit
1 Celsius
0330 Daylight savings 1 Auto-change to daylight
savings time (through
2006)
2 Auto-change to daylight
savings time (2007 and
beyond)
0 Daylight savings time is
turned off
0340 Remote sensor 0 No remote sensor
1 Outdoor sensor (display
only)
2 Outdoor sensor for con-
trol (select heat pumps)
3 Indoor sensor
0350 Heat pump com-
pressor lockout
0 Off
[Other options: 15, 20,
25, 30, 35, 40°F (-9.5°C
to 7°C)]
0360 Heat pump auxil-
iary lockout
0 Off
[Other options: 40, 45,
50, 55, 60°F (4.5°C to
15.5°C)]
0380 Dehumidication
Control
0 Off
1 A/C runs to help
dehumidify
0500 Furnace lter
change reminder
0 Off
1 10-day run time
(about 1 month)
2 30-day run time
(about 3 months)
3 60-day run time
(about 6 months)
4 90-day run time
(about 9 months)
5 120-day run time
(about 1 year)
6 365-day run time
(about 3 years)
0510 Humidier pad
change reminder
0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days