Honeywell 3355 Thermostat User Manual


 
28
69-1012
Step 10: Check Thermostat Operation after Programming and Installing
Heating
Do
not
check heating system
operation by jumpering thermostat
terminals at the primary control
such as the gas valve, zone valve,
or oil burner control. This damages
the thermostat, instead, jumper R
and W wires at the thermostat.
Move the system switch to HEAT
and the fan switch to AUTO.
Press key until the setting is about
10°F (6°C) above room tempera-
ture. Heating should start and the
fan should run after a short delay
(immediately if fan operation switch
is set in E position).
Press key until setting is about 10°F
(6°C) below room temperature. The
heating equipment should shut off.
HeatCool Off
Auto On
Warmer
Cooler