50 Hz Performance
Model
Capacity
BTUH/watts
6°C TD
-29°C SST
Fan Data
Standard Motor Data
Defrost Heaters (Std.)
HP
Total Amps
Watts
Total Amps
CFM/m
3
h No.
Dia.
in./mm
Air Throw ft./m 220/1/50 380/1/50
380
/3/50
380
/1/50
Standard
w/
Collar
Wired
1-Phase
Wired
1-Phase
Wired
3-Phase
BHG Models 6 Fins Per Inch
BHG450 41,400 12,100 8,100 23,400 2 24 610 60 18 80 24 1/2* 6.4 3.4 - 2.6 1,430 3.8
BHG550 50,600 14,800 8,100 23,400 2 24 610 60 18 80 24 1/2* 6.4 3.4 - 2.6 1,430 3.8
BHG640 58,900 17,300 11,300 32,700 3 24 610 60 18 80 24 1/2* 9.6 - 3.0 3.9 1,840 4.9
BHG740 68,100 19,900 11,300 32,700 3 24 610 60 18 80 24 1/2* 9.6 - 3.0 3.9 1,840 4.9
BHG810 74,500 21,800 15,100 43,800 4 24 610 60 18 80 24 1/2* 12.8 - 4.7 5.2 2,730 7.2
BHG950 87,400 25,600 15,100 43,800 4 24 610 60 18 80 24 1/2* 12.8 - 4.7 5.2 2,730 7.2
BHG1020 93,800 27,500 18,600 53,900 3 30 762 90 27 100 30 1 - - - 6.9 2,730 7.2
BHG1200 110,400 32,300 18,600 53,900 3 30 762 90 27 100 30 1 - - - 6.9 2,730 7.2
BHG1390 127,900 37,500 21,900 63,200 3 30 762 90 27 100 30 1-1/2 - - - 9.9 2,730 7.2
BHG1650 151,800 44,500 23,900 69,000 3 30 762 110 34 130 40 1-1/2 - - - 10.5 2,870 7.5
BHG2120 195,000 57,100 31,900 92,100 4 30 762 110 34 130 40 1-1/2 - - - 14.0 4,230 11.1
BHF Models 4 Fins Per Inch
BHF400 36,800 10,800 8,500 24,500 2 24 610 60 18 80 24 1/2* 6.4 3.4 - 2.6 1,430 3.8
BHF480 44,200 12,900 8,500 24,500 2 24 610 60 18 80 24 1/2* 6.4 3.4 - 2.6 1,430 3.8
BHF560 51,500 15,100 11,900 34,300 3 24 610 60 18 80 24 1/2* 9.6 - 3.0 3.9 1,840 4.9
BHF650 59,800 17,500 11,900 34,300 3 24 610 60 18 80 24 1/2* 9.6 - 3.0 3.9 1,840 4.9
BHF710 65,300 19,100 15,900 45,700 4 24 610 60 18 80 24 1/2* 12.8 - 4.7 5.2 2,730 7.2
BHF840 77,300 22,600 15,900 45,700 4 24 610 60 18 80 24 1/2* 12.8 - 4.7 5.2 2,730 7.2
BHF890 81,900 24,000 19,500 56,200 3 30 762 90 27 100 30 1 - - - 6.9 2,730 7.2
BHF1050 96,600 28,300 19,500 56,200 3 30 762 90 27 100 30 1 - - - 6.9 2,730 7.2
BHF1220 112,200 32,900 22,700 65,500 3 30 762 90 27 100 30 1-1/2 - - - 9.9 2,730 7.2
BHF1440 132,500 38,800 24,900 71,800 3 30 762 110 34 130 40 1-1/2 - - - 10.5 2,870 7.5
BHF1860 171,100 50,100 33,100 95,800 4 30 762 110 34 130 40 1-1/2 - - - 14.0 4,230 11.1
Table 8. Models BHG/BHF 50 Hz Hot Gas Defrost
* 380/3/50 motors are 3/4 HP
Hot gas drain pan available
Notes: TD = Temperature Dierence = (Room temperature - saturated suction temperature)
Saturated Suction Temperature °F +20 -10 -20 -30 -40
Saturated Suction Temperature °C -7 -23 -29 -34 -40
Multiply Capacity By 1.15 1.04 1.00 0.90 0.80
Capacity Correction Factors for Electric and Hot Gas Defrost Units