Heat & Glo LifeStyle FB-GRAND-S Indoor Fireplace User Manual


 
Heat & Glo • FB-IN-S, FB-GRAND-S • 783-910 Rev. D • 3/08
9
CAUTION
ALL vent speci cations MUST be followed.
This product is tested and listed to these speci cations.
Appliance performance will suffer if speci cations are not
followed.
Figure 5.1
C. Measuring Standards
Vertical measurements listed in the vent diagram (Figure
5.1) were made using the following standard:
• Vertical terminations are measured to top of chimney.
Fire Hazard.
Explosion Risk.
Asphyxiation Risk.
Do NOT connect this gas appliance to a
chimney ue serving a separate solid fuel or
gas burning appliance.
May impair safe operation of this appliance
or other appliances connected to the ue.
Vent this appliance directly outside.
Use separate vent system for this appliance.
B. Horizontal Venting
Horizontal venting is NOT allowed.
5
5
Vent Information and Diagrams
A. Vent Table Key
The abbreviations listed in this vent table key are used in
the vent diagrams.
Symbol Description
V
MIN
Minimum Vertical Run Length 14 ft.
V
MAX
Maximum Vertical Run Length 50 ft.
WARNING
TERMINATION
CAP
ADAPTOR
EXHAUST
VENT PIPE
V= 14 FT. MINIMUM
50 FT. MAXIMUM
3 INCH COLLAR
(Factory installed to
stainless steel section)
WARNING: DO NOT
BLOCK PIPE END WITH
INSULATION OR ANY OTHER
SEALING MATERIAL
STAINLESS STEEL
PIPE - 3 FT. MIN.
REQUIRED (INCLUDED)
INLET AIR
VENT PIPE
COLLAR ATTACHMENT
BRACKET
EXHAUST COLLAR
INLET AIR COLLAR
Note: To achieve optimum
performance of insert,
minimize or avoid bends
in exhaust vent pipe.