Heat & Glo LifeStyle EXCLAIM-36T-C Indoor Fireplace User Manual


 
Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06
11
C. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the replace opening. See Figure 3.3.
If you are using a decorative surround constructed of combustible material, it must be located within the shaded area de-
ned in Figure 3.3. Short stub walls are also acceptable if they are contained within the shaded area.
D. Frame the Fireplace
Figure 3.4 shows a typical framing (using 2 x 4 lumber) of the replace, assuming combustible materials are used. All re-
quired clearances to combustibles around the replace must be adhered to. See Figure 3.2. Any framing across the top of
the replace must be above the level of the top standoffs.
23-3/4 in.
(603 mm)
50°
12 in.
(305 mm)
36 in.
(914 mm)
(opening)
45-1/2 in.
(1156 mm)
(framing)
39°
4 in.
(102 mm)
BRICK
FRONT
FLUSH FRONT
12 in.
(305 mm)
19-3/4 in.
(502 mm)
Figure 3.3 Sidewalls and Surrounds
Note: Fireplace header
cannot be positioned
until the fireplace
assembly is in place.
28 in.
(711 mm)
49-3/4 in.
(1264 mm)
45-1/2 in.
(1156 mm)
49-3/4 in. (1264 mm)
header height. Use
only noncombustible
material below the top
of the front standoffs.
2 in. (51 mm)
minimum air
space clearance
to the enclosure.
Figure 3.4 Framing the Fireplace
Note: The frame of the
AED door overlaps the
front of the fireplace
beyond the opening by
3/4 in. (19 mm) on each
side and 1-1/2 in. (38 mm)
above the top. This should
be allowed for when apply-
ing facing to the front of the
replace.
¨