Heat Controller VMC12SB-1/VMH12SB-1 Heat Pump User Manual


 
- 51 -
Only for training and service purposes
Part 4 Trouble Shooting
Cause of error
6
Supplied power is not normal
Comp Connector (CN-U,V,W) is disconnected or inserted into the
wrong
position
Compressor is damaged (coil short) replace compressor
Too much Refrigerant
Defect in outdoor pcb assembly replace pcb assembly
DC Peak Error
Supplied voltage to
Outdoor pcb is about
AC 208~230V ?
Is connector (CN-U,V,W)
connected to compressor and
inserted into the pcb in right position ?
YES
No
Check power source
No
Check CN-U,V,W connector
(U : RD, V : BL, W : YL)
Check flow
Refrigerant pressure is right ?
YES
No
Check refrigerant pressure
and adjust.
Is the compressor right ?
YES
No
Check resistance
Between U-V, V-W, U-W port.
Short / Open circuit
(Comp.motor coil error)
normal : 1 ~2
Between U,V,W and Body
normal : over 10M
Inverter components in outdoor pcb assembly are
right ?
YES
No
* 9 K/12K Model
Check
Short of SPM3 pins (GND - P, U, V, W pin)
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z
Assembling state of R01P ~ R21P & IC01P
Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.
V
U
W
Description Cause of error
Error code