Heat Controller VMC09SB-1/VMH09SB-1 Heat Pump User Manual


 
- 54 -
Only for training and service purposes
Part 4 Trouble Shooting
10
Discharge pipe temp. is short or open
Discharge pipe temp. is not connected to the outdoor pcb assembly
Damage or defect on the sensing circuit of outdoor pcb assembly
Discharge pipe temp. is
short or open
Discharge pipe temp. is connected
to Outdoor pcb assembly ?
Discharge pipe temp. is right ?
YES
No
Connect to CN-D_PIPE
in outdoor pcb assembly
Sensing circuit of outdoor
pcb is right ?
No
Check Discharge pipe temp.
-
Measure resistance of thermistor
(about 200k at 25°C(77°F)).
YES
No
- Check soldering state of
R07H, R08H, C04H
Check flow
Description Cause of error
Error code