Heat Controller TGC048C-4K-135 Heating System User Manual


 
NOMINAL 3.5 TONS
Model
TGC042C-1K-120 TGC042C-3K-120 TGC042C-4K-120
Cooling Performance
1
Gross Cooling Capacity Btuh 43000 43000 43000
EER/SEER
2
11.45/13 11.45/13 11.45/13
Nominal CFM/ARI Rated CFM 1400/1450 1400/1450 1400/1450
ARI Net Cooling Capacity Btuh 41000 41000 41000
Net Sensible Capacity Btuh 30000 30000 30000
Net Latent Capacity Btuh 11000 11000 11000
Net System Power kW 3.59 3.59 3.59
Heating Performance (Package Gas/Electric)
3
Heating Input Btuh 120000 120000 120000
Heating Output Btuh 94500 97200 97200
Temperature Rise ºF 50-80 50-80 50-80
AFUE (%) 80 80 80
Steady State Efficiency (%) 81 81 81
Qty of Burners 6 6 6
Qty of Stages 1 1 1
Gas Connection Pipe Size, in. .5 .5 .5
Compressor
Qty/Type
Outdoor Sound Rating (dB) 78 78 78
Outdoor Coil—Fin Type
Tube Type Rifled Rifled Rifled
Tube Size in. OD 0.375 0.375 0.375
Face Area sq. ft. 16.91 16.91 16.91
Rows / Fins per inch 1.53/22 1.53/22 1.53/22
Indoor Coil—Fin Type
Tube Type Rifled Rifled Rifled
Tube Size in. 0.375 0.375 0.375
Face Area sq. ft. 5.17 5.17 5.17
Rows / Fins per inch 3/13 3/13 3/13
Refrigerant Control TXV TXV TXV
Drain Connection Qty/Size, in. 1/0.75 1/0.75 1/0.75
Outdoor Fan—Type
Qty Used/Diameter in. 1/24 1/24 1/24
Drive Type/Speeds Direct/1 Direct/1 Direct/1
CFM 3680 3680 3680
Qty Motors-HP 1-1/3 1-1/3 1-1/3
Motor RPM 1075 1075 1075
Indoor Fan—Type
Qty Used/Diameter in. 1/10x10 1/10x10 1/10x10
Drive Type/Speeds Direct/3 Direct/3 Direct/3
Motor Qty 1 1 1
Motor HP 1/2 1/2 1/2
Motor RPM 1725 1725 1725
Motor Frame Size 48 48 48
Filter—Type
Furnished Yes Yes Yes
(Qty) Size Recommended in. (2)16x25x1 (2)16x25x1 (2)16x25x1
Refrigerant Charge Oz. 117 117 117
Weights
Net Weight lbs. 579 579 579
Ship Weight lbs. 586 586 586
Notes:
Forward Curved Centrifugal
Disposable
1/Copeland Scroll
Louvered
Corrugated
Propeller
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan
motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units
are certified and rated per ARI Standard 210/240.
2. EER/SEER are rated ARI condition and accordance with DOE test procedures.
3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National
Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each
1000 feet above sea level.
GENERAL DATA
8
Heat Controller, Inc.
-8-