Heat Controller CDG SERIES Heat Pump User Manual


 
Heat Controller, Inc. INSTALLATION INSTRUCTIONS Cased/Uncased Coils
10
6.0 Refrigerant Connections
To prevent refrigerant leak, use proper tools to ensure clean, burr-free cut.
Use brazing shield when welding close to the cabinet surface and wet rag to protect rubber grommet.
Brazing alloy should be at least 5% silver content.
6.1 Flowrator Piston Change
In most applications, there is no need to change the piston (orice). However, in some applications,
changing the piston size is required. If the application requires a different piston/owrator, change the
piston in the distributor of indoor coil before installing the coil. See Table 1 for orice size.
To change the piston, use following steps:
1. Remove cover panel.
2. Use Two wrenches.
Loosen one turn to release pressure. (High pressure gas)
3. After releasing pressure.
Loosen and carefully pull a part the two ttings to expose piston.
4. Remove factory installed piston and replace with recommended piston from Table 1 as shown in Fig.7.
5. Carefully reassemble assembly. (Hand tighten)
Be sure to use teon tape on thread for a complete seal.
6. Hand tighten and make sure assembly is properly connected and then torque to 10-30 ft/lb.
NOTE: Be careful not to bend tubing
NUT
(MOMENT:15±2N.m)
PISTON
LIQUID LINE
Fig. 7: Flowrator Piston Change