Heat Controller A-VMH36QC-1 Air Conditioner User Manual


 
34
Service Manual VMH SerieS Heat Controller, Inc.
9.3.2.2 Voltage protection (ODU E5)
Voltage protection
Check the voltage of
outdoor unit power supply,
whether the voltage
between L(L1) and N (L2) is
about 220~240VAC
Check the power supply
Check whether the voltage
of IPM board P and N is
normal? DC277-356V for
18-27KBtu/h; DC277-410V
for 36KBtu/h
Replace bridge rectifiers,
and then check whether the
system can run normally
Replace IPM board, and
then check whether the
system can run normally
Replace outdoor main board
Yes
No
No
No
No
Yes
Trouble is solved
Yes
Yes